P#
DESCRIPTION
041
Relay operating mode in HD45
models
and CO
mode
in
simplified mode disabled.
In HD45 models, this is the mode with
rotary selector in position 0.
In HD46 models, this is the mode when
the
threshold
disabled.
042
Temperature relay operating mode
in HD46 models with simplified
mode disabled.
043
Humidity relay operating mode in
HD46 models with simplified mode
disabled.
044
Threshold B relay in HD45 and CO
relay in HD46 (relay activated below
threshold)
Thres. is in ppm if associated with CO
Threshold is x10 if associated with
humidity or temperature in HD45
045
Threshold B (x10) temp. relay in
HD46 (relay activated below thres.)
046
Threshold B (x10) humidity relay in
HD46 (relay activated below thres.)
047
Threshold A relay in HD45 and CO
relay in HD46 (relay activated over
threshold)
Thres. is in ppm if associated with CO
Threshold is x10 if associated with
humidity or temperature in HD45.
048
Threshold A (x10) temp. relay in
HD46 (relay activated over thres.)
049
Threshold A (x10) humidity relay in
HD46 (relay activated over thres.)
relay operating
2
HD46
models
with
simplified
setting
VALUE
00: always disabled
01: active below threshold B
02: active over threshold A
03: active over threshold A
and below threshold B
05: active below threshold B
with hysteresis
06: active over threshold A
is
with hysteresis
07: active over threshold A
and below threshold B
with hysteresis
08: active only if in error
09: active below threshold B
and if in error
0A: active over threshold A
0B: active over threshold A,
below threshold B and if
in error
0D: active below threshold B
with hyster. and in error
0E: active over threshold A
with hyster. and in error
0F: active over threshold A
and below threshold B
with hyster. and in error
FF: always enabled
As P#041
As P#041
Over the whole range
2
.
2
Over the whole range
Over the whole range
Over the whole range
2
.
2
Over the whole range
Over the whole range
- 32 -
DEFAULT
NOTE
06
(6)
05
06
(3),(4)
1000
(6)
200
(3),(4)
500
(3),(4)
(3),(4)
1000
(6)
200
(3),(4)
500
(3),(4)