Mitsubishi Electric Mr. Slim PCA Series Service Manual page 4

Split-type, heat pump air conditioners
Hide thumbs Also See for Mr. Slim PCA Series:
Table of Contents

Advertisement

[1] Cautions for service
· After recovering the all refrigerant in the unit, proceed to working.
· Do not release refrigerant in the air.
· After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.
[2] Refrigerant recharging
(1) Refrigerant recharging process
1Direct charging from the cylinder.
· R407C cylinder are available on the market has a syphon pipe.
· Leave the syphon pipe cylinder standing and recharge it.
(By liquid refrigerant)
(2) Recharge in refrigerant leakage case
· After recovering the all refrigerant in the unit, proceed to working.
· Do not release the refrigerant in the air.
· After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.
[3] Service tools
Use the below service tools as exclusive tools for R407C refrigerant.
No.
1
Gauge manifold
2
Charge hose
3
Electronic scale
4
Gas leak detector
5
Adaptor for reverse flow check
6
Refrigerant charge base
7
Refrigerant cylinder
8
Refrigerant recovery equipment
Gravimeter
Tool name
· Only for R407C
· Use the existing fitting SPECIFICATIONS. (UNF7/16)
· Use high-tension side pressure of 3.43MPa·G or over.
· Only for R407C
· Use pressure performance of 5.10MPa·G or over.
· Use the detector for R134a or R407C.
· Attach on vacuum pump.
· For R407C
· Top of cylinder (Brown)
· Cylinder with syphon
4
Unit
Specifications

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mr. slim pca-rp71haqMr. slim pca-rp125haq

Table of Contents