Mitsubishi Electric CITY MULTI PLFY-P15VFM-E Technical & Service Manual page 25

Split-type, heat pump air conditioners
Table of Contents

Advertisement

Switch
Pole
Function
1
Setting ceilling height Depends on SW21-1, SW21-2
2
3
4
5
SW21
6
Function
selection
1
2
3 Pair No. of wireless remote controller
4 Pair No. of wireless remote controller
• To operate each indoor unit by each remote controller when
installed 2 indoor units or more are near, Pair No. setting is
necessary.
●Pair No. setting is available with the 4 patterns (Setting patterns A to D).
●Make setting for J41, J42 of indoor controller board and the Pair
No. of wireless remote controller.
• You may not set it when operating it by one remote controller.
Setting for indoor unit
●Cut jumper wire J41, J42 on the indoor controller board
according to the table below.
SW22
Wireless remote controller pair number:
Function
●Setting operation
selection
1. Press the SET button (using a pointed implement). Check that
the remote controller's display has stopped before continuing.
MODEL SELECT flashes, and the model No. (3 digits) appears
(steadily-lit).
2. Press the MINUTE button twice. The pair number appears
flashing.
3. Press the temperature
4. Press the SET button (using a pointed implement). The set
pair number is displayed (steadily-lit) for 3 seconds, then
disappears.
Indoor unit SW22
SW22-3
ON
OFF
ON
OFF
Drain pump and fan are activated simultaneously after the
connector SWE is set to ON and turn on the power.
SWE
OFF
Test run
for Drain
The connector SWE is set to OFF after test run.
pump
OCH601
Operation by switch
ON
SW21-1
Silent
Standard
OFF
High
ON
Function
buttons to select the pair number to set.
Pair No. of wireless
remote controller
SW22-4
ON
0
ON
1
OFF
2
OFF
3–9
SWE
ON
Effective
timing
OFF
operation
suspension
SW21-2
ON
OFF
2.7 m (default setting)
OFF
ON
OFF
Depends on SW22-3, 22-4
Under
operation
suspension
Initial setting
SWE
OFF
ON
Under
operation
25
Remarks
<Initial setting>
Under
ON
or
OFF
1 2 3 4 5 6
Height
2.5 m
3.0 m
<Initial setting>
ON
OFF
1 2 3 4
MODEL SELECT
ON/OFF
TEMP
FAN
AUTO STOP
or
AUTO START
MODE
VANE
CHECK LOUVER
TEST RUN
SET
RESET
CLOCK
SET button
<Initial setting>
SWE
OFF
ON
Pair No.
Model No.
Temperature
button
h
Minute
button
min