Specifications - Mitsubishi Electric Mr. Slim PUHZ-SHW230YKA Service Manual

Split-type, air to water heat pump
Table of Contents

Advertisement

2

SPECIFICATIONS

2-1. SPECIFICATION
2.-1-1. PUHZ-SHW230YKA
<Reference data> Plate heat exchanger (MWA2-38PA) *2pcs [connected in parallel]
Nominal water fl ow
Heating
Capacity
(A7/W35)
COP
Power input
Heating
Capacity
(A7/W45)
COP
Power input
Heating
Capacity
(A2/W35)
COP
Power input
Heating
Capacity
(A2/W45)
COP
Power input
Nominal water fl ow
Cooling
Capacity
(A35/W7)
EER
Power input
Cooling
Capacity
(A35/W18)
EER
Power input
Note: "COP" and "Power input" in the above table are the values that do NOT contain the "pump input (based on EN 14511)".
OCH534
L/min
65.9
kW
23.0
3.65
kW
6.31
kW
23.0
2.77
kW
8.29
kW
23.0
2.37
kW
9.69
kW
23.0
2.02
kW
11.4
L/min
57.3
kW
20.00
2.22
kW
9.01
kW
20.00
3.55
kW
5.64
5
Rating conditions
Nominal operating condition
Heating (A2/W35)
Outside air temperature (Dry-bulb)
Outside air temperature (Wet-bulb)
Water temperature (inlet/outlet)
Heating (A2/W45)
Outside air temperature (Dry-bulb)
Outside air temperature (Wet-bulb)
Water temperature (inlet/outlet)
Heating (A7/W35)
Outside air temperature (Dry-bulb)
Outside air temperature (Wet-bulb)
Water temperature (inlet/outlet)
Heating (A7/W45)
Outside air temperature (Dry-bulb)
Outside air temperature (Wet-bulb)
Water temperature (inlet/outlet)
Cooling (A35/W7)
Outside air temperature (Dry-bulb)
Outside air temperature (Wet-bulb)
Water temperature (inlet/outlet)
Cooling (A35/W18)
Outside air temperature (Dry-bulb)
Outside air temperature (Wet-bulb)
Water temperature (inlet/outlet)
+ 2 °C
+ 1 °C
+ 30 °C/+ 35 °C
+ 2 °C
+ 1 °C
+ 40 °C/+ 35 °C
+ 7 °C
+ 6 °C
+ 30 °C/+ 35 °C
+ 7 °C
+ 6 °C
+ 40 °C/+ 45 °C
+ 35 °C
+ 24 °C
+ 12 °C/+ 7 °C
+ 35 °C
+ 24 °C
+ 23 °C/+ 18 °C

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mr. slim pu-shw230yka

Table of Contents