Rheem Raypak Delta Limited 399B Installation & Operating Instructions Manual page 26

Hide thumbs Also See for Raypak Delta Limited 399B:
Table of Contents

Advertisement

Use insulated vent pipe spacers where the vent pass-
es through combustible roofs and walls.
Vent Terminal Location
1. Condensate can freeze on the vent cap. Frozen
condensate on the vent cap can result in a blocked
flue condition.
2. Give special attention to the location of the vent
termination to avoid possibility of property dam-
age or personal injury.
3. Gases may form a white vapor plume in winter.
The plume could obstruct a window view if the
termination is installed near windows.
4. Prevailing winds, in combination with below-freez-
ing
temperatures,
condensate and water/ice build-up on buildings,
plants or roofs.
5. The bottom of the vent terminal and the air intake
shall be located at least 12 in. above grade, includ-
ing normal snow line.
6. Un-insulated single-wall metal vent pipe shall not
be used outdoors in cold climates for venting gas-
fired equipment.
7. Through-the-wall vents for Category II and IV
appliances and non-categorized condensing
appli-ances shall not terminate over public walk-
ways or over an area where condensate or vapor
could create a nuisance or hazard or could be
detrimental to the operation of regulators, relief
valves, or other equipment. Where local experi-
ence indicates that condensate is a problem with
Category I and III appliances, this provision shall
also apply.
Combustion
Air Supply
From Inside Building
From Outside Building
can
cause
freezing
Exhaust
Configuration
Vertical Natural
Draft Venting
Horizontal Through-
the-Wall Venting
Vertical Natural
Draft Venting
Horizontal Through-
the-Wall Venting
Table K: Venting Category Requirements
UNCONTROLLED DOCUMENT IF PRINTED
APPROVED
8. Locate and guard vent termination to prevent
acci-dental contact by people or pets.
9. DO NOT terminate vent in window well, stairwell,
alcove, courtyard or other recessed area.
10. DO NOT terminate above any door, window, or
gravity air intake. Condensate can freeze, causing
ice formations.
11. Locate or guard vent to prevent condensate from
damaging exterior finishes. Use a rust-resistant
sheet metal backing plate against brick or mason-
ry surfaces.
12. DO NOT extend exposed vent pipe outside of
building. Condensate could freeze and block vent
pipe.
of
U.S. Installations
Refer to the latest edition of the National Fuel Gas
Code.
Vent termination requirements are as follows:
1. Vent must terminate at least 4 ft below, 4 ft
hori-zontally from or 1 ft above any door, window
or gravity air inlet to the building.
2. The vent must not be less than 7 ft above grade
when located adjacent to public walkways.
3. Terminate vent at least 3 ft above any forced air
inlet located within 10 ft.
4. Vent must terminate at least 4 ft horizontally, and
in no case above or below unless 4 ft horizontal
distance is maintained, from electric meters, gas
meters, regulators, and relief equipment.
Heater Venting
Certified
Category
Materials
I
"B" Vent
Stainless Steel
III
(Gas Tight)
I
"B" Vent
Stainless Steel
III
(Gas Tight)
26
Combustion Air
Inlet Material
Galvanized Steel
PVC
ABS
CPVC

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents