Pipe connections between indoor and outdoor unit
Refrigerant piping system
Y branch method
1 Outdoor Units
Example : 5 Indoor Units connected
?
: Outdoor Unit
?
: 1st branch (Y branch)
: Indoor Units
C
2 Outdoor Units
Example : 5 Indoor Units connected
?
: Outdoor Unit
?
: 1st branch (Y branch)
: Indoor Units
C
: Downward Indoor Unit
D
?
: Connection branch pipe
between Outdoor units:
ARCNN21
Piping length from outdoor branch to outdoor unit ≤10m, equivalent length:max 13m
(for 22HP or more)
Additional Application
To satisfy below condition to make 40 m ~ 90 m of pipe length after first branch.
1) Diameter of pipes between first branch and the last branch should be increased by one step,
except pipe diameter B,C,D is same as Diameter A
Ø6.35
Ø 9.52
38.1*
* : It is not necessary to size up.
2) While calculating whole refrigerant pipe length, pipe B,C,D length should be calculated twice.
A+Bx2+Cx2+Dx2+a+b+c+d+e ≤ 1,000 m
3) Length of pipe from each indoor unit to the closest branch (a,b,c,d,e) ≤ 40 m
4) [Length of pipe from outdoor unit to the farthest indoor unit 5 (A+B+C+D+e)]
- [Length of pipe outdoor unit to the closest indoor unit 1 (A+a)] ≤ 40 m
30
Outdoor Unit
Ø 12.7
Ø 15.88
Ø 19.05
L150m (200 m : Conditional application)
l 40m (90 m : Conditional application)
Slave
Slave
Master
Master
10m or
less
L150m (200 m : Conditional application)
l 40m (90 m : Conditional application)
Ø 22.2
Ø 25.4*, Ø 28.58
Slave
Master
ODU Capacity
Master Slave
Ø 31.8*, Ø 34.9
Ø