INSTALLATION DIAGRAM OF INDOOR AND OUTDOOR UNITS

3
Batteries
Flat head
wood screw
2
Wireless remote control
RAS-05, 07, 10, 13J2AVG-TR
RAS-16, 18J2AVG-TR
RAS-05, 07, 10, 13J2AVG-EE
RAS-16, 18J2AVG-EE
RAS-05, 07, 10, 13TAVG-EE
RAS-16, 18TAVG-EE
C
600
D
400
E
45
F
100

Optional Installation Parts

Part
Parts name
code
Refrigerant piping
Liquid side : Ø6.35 mm
(RAS-05, 07, 10, 13J2KVG-TR)
(RAS-05, 07, 10, 13J2KVG-EE)
(RAS-05, 07, 10, 13TKVG-EE)
A
Gas side : Ø12.70 mm
(RAS-16, 18J2KVG-TR)
(RAS-16, 18J2KVG-EE)
(RAS-16, 18TKVG-EE)
Pipe insulating material
B
(polyethylene foam, 6 mm thick)
Putty, PVC tapes
C
1122950109_S04_182x257_52p_S_p70_181217_EN+TR+RU.indd 7
Refrigerant piping
must be protected from
physical damage.
Install a plastic cover or
equivalent.
Vinyl tape
Apply after carrying
6
out a drainage test.
4
Remote control
holder
600
600
100
100
Q'ty
One
each
1
One
each
Hook
1
Installation
plate
Shield pipe
Saddle
Extension drain hose
(Not available, provided
by installer)
Fixing bolt arrangement of outdoor unit
• Secure the outdoor unit with fixing bolts and nuts if the unit is likely to be
exposed to a strong wind.
• Use Ø8 mm or Ø10 mm anchor bolts and nuts.
• If it is necessary to drain the defrost water, attach drain nipple
water proof
10
to the bottom plate of the outdoor unit before installing it.
500 mm
Air inlet
97 mm
Air outlet
Drain outlet
RAS-05, 07, 10, 13J2AVG-TR
RAS-05, 07, 10, 13J2AVG-EE
RAS-05, 07, 10, 13TAVG-EE
5
For the rear left, bottom left and left piping
Wall
Cut out a piece of SPACER from indoor
unit packaging box, roll it and insert
between the indoor unit and wall to tilt
the indoor unit for better operation.
The auxiliary piping can be connected to
the left, rear left, rear right, right, bottom
right or bottom left.
Right
Rear
right
Left
Bottom
Rear
right
left
Bottom left
Do not allow the drain hose to get slack.
Cut the piping
hole sloped
slightly.
Make sure to run the drain hose sloped
downward.
Insulate the refrigerant pipes separately
with insulation, not together.
6 mm thick heat resisting
polyethylene foam
and cap
9
108 mm
125 mm
28 mm
Air inlet
Air outlet
90 mm
600 mm
Drain outlet
RAS-16, 18J2AVG-TR
RAS-16, 18J2AVG-EE
RAS-16, 18TAVG-EE