[ VII Control ]
Startup sequence rotation
-2- Initial control
When the power is turned on, the initial processing of the microcomputer is given top priority.
During the initial processing, processing of the operation signal is suspended and is resumed after the initial processing is
completed.
(Initial processing involves data processing by the microcomputer and initial setup of the LEV opening. This process takes up
to two minutes.)
During the initial processing "
Initial Control
-3- Compressor frequency
The upper limit of frequency during the first 30 seconds of operation is 48 Hz.
The upper limit of frequency during the first 90 seconds of operation is 60 Hz.
If the water temperature is controlled based on the outlet water temperature (SW3-3 is set to OFF.), for 90 seconds after the
startup, the compressor will be controlled every 30 seconds so that the frequency fluctuation will be kept within ± 5 Hz.
If the water temperature is controlled based on the external water temperature sensor reading or the inlet water temperature
(SW3-3 is set to ON.), for 90 seconds after the startup, the compressor will be controlled every 30 seconds so that the fre-
quency fluctuation will be kept within ± 10 Hz.
(The above does not apply when the high-pressure is suppressed to protect the system or when the defrost operation is in
progress.)
The amount of frequency change is controlled to approximate the target value that are determined based on the temperature
difference between the current and the preset water temperatures.
The minimum operating frequency is 30 Hz.
The maximum frequency will be determined based on the relationship between the water temperature and the outside tem-
perature as well as the ON/OFF status of the Energy-save/Maximum capacity contact.
(The values not on listed in the table are interpolated.)
"Energy-save/Maximum capacity" contact is ON.
− 20
− 15
− 5
35
100
100
100
Water
45
100
100
100
temperature
60
100
100
100
°C
70
100
100
100
HWE15070
" will appear on the LED monitor on the MAIN board.
(Maximum frequency of the compressor Hz)
Outside temp.
°C
0
5
10
15
20
25
30
100
77
65
57
53
49
46
100
82
69
60
55
51
48
100
88
76
69
63
58
53
100
95
84
75
68
62
57
"Energy-save/Maximum capacity" contact is OFF.
− 20
− 15
35 or above
43
35
100
100
Water
44
45
100
100
temperature
49
60
100
100
°C
50
70
100
100
- 89 -
(Maximum frequency of the compressor Hz)
Outside temp.
°C
− 5
0
5
10
15
20
25
100
100
100
91
85
81
76
100
100
100
94
88
83
78
100
100
100
100
93
87
81
100
100
100
100
96
90
83
30
35 or above
71
66
73
67
75
69
77
71