Summary of Contents for BIFFI ICON 2000
Page 1
2000 INSTRUCTION HANDBOOK MAN 618 MAN 618...
Page 3
Revised document R. Marchelli G. Alfieri Rev. Date Description Prepared Approved NOTES: BIFFI Italia has taken every care in collecting and verifying the documentation contained in this instruction and operating manual. The information herein contained is reserved property of BIFFI Italia.
ICON2000 electric actuators covered in this I&O Manual are designed for the operation of any kind of industrial valves used in heavy industrial, chemical, petrochemical plants. Biffi will not be liable for any possible damage resulting from use in other than the designated applications.
ATEX Directive 4. Terms and conditions Biffi guarantees each single product to be free from defects and to conform to current goods specifications. The warranty period is one year from the date of installation by the first user, or eighteen months from the date of shipment to the first user, whichever occurs first.
BIFFI actuators are weatherproof to IP 66/IP 68. This condition can only be maintained if the units are correctly installed/connected on site and if they have been correctly stored.
The removal of any other covers without Biffi's approval will invalidate the warranty. Biffi will not accept any responsibility for any damage or deterioration that may be caused. Important: All the accessories (in particular cable glands) must be certified.
8. Terminal board Important: The removal of any other covers without Biffi's approval will invalidate the warranty. Biffi will not accept any responsibility for any damage or deterioration that may occur as a result of cover removal.
Use “View” mode to see the actuator configuration, and use “Set-up” mode to change the present configuration. Unauthorised access to the set-up mode is prevented by a 4- character alphanumeric password. The actuator is supplied by BIFFI with the default password “ 0 0 0 0 “.
• set data logger 3.1 SET PASSWORD The actuator is supplied by BIFFI with a default password (“0 0 0 0”). By the above routine the end user can enter a different password consisting of 4 alphanumeric characters. After entering the new password, the old one ceases to be valid. Therefore it is mandatory “NOT TO FORGET THE PASSWORD”...
The following data may be viewed: Serial number: max. 28 characters, univocal identifier of the actuator by reference to BIFFI acknowledgment. Actuator type: max. 28 characters, describes the type of actuator with reference to BIFFI catalogue Torque / Thrust: nominal torque or thrust of actuator...
2. Special maintenance In case actuator failure, please refer to Section 618/3 chapter N for possible causes. Spare parts can be required to BIFFI: please refer to the individual item number shown in Section 618/4. Note: Special maintenance is also recommended when, during operations, the actuator generates an excessive noise.
“ICON2000” instruction and operating manual TROUBLE-SHOOTING The ICON2000 actuator has passed the functional test performed by Biffi Quality Assurance personnel. Warning: The actuator is non-intrusive. The control compartment was sealed in dry and clean conditions and contains no site serviceable components. Do not open it unless absolutely necessary.
Page 101
BUS OK CONFIGURATION OBJ n°: n° indicates the number of the parameter to be configured. To clear the alarm the table of all ICON2000 parameters is necessary. Call BIFFI After-sales service to solve the problem. If the alarm message is “CONFIGURATION OBJ 9999” only one of the ICON2000 parameters needs to be changed.
Page 124
EN 13463-5: 2003 Terms and conditions Biffi Italia guarantees each single product to be free from defects and to conform to current goods specifications. Except when differently specified, the warranty period in one year from the date of installation by the first user, or eighteen months from the date of shipment to the first user, whichever occurs first.
Page 125
Normally the optional extension for additional entry/entries or additional electronic card are directly mounted on the base ICON2000/ICON2000AD by BIFFI and leaves the factory in perfect condition. Under this condition the general storage procedure as stated on the base INSTRUCTION HANDBOOK MAN 618 must be applied.
Page 142
EN 13463-5: 2003 Terms and conditions Biffi Italia guarantees each single product to be free from defects and to conform to current goods specifications. Except when differently specified, the warranty period in one year from the date of installation by the first user, or eighteen months from the date of shipment to the first user, whichever occurs first.
Page 143
Normally the optional extension for additional entry/entries or additional electronic card are directly mounted on the base ICON2000/ICON2000AD by BIFFI and leaves the factory in perfect condition. Under this condition the general storage procedure as stated on the base INSTRUCTION HANDBOOK MAN 618 must be applied.
Page 152
In case the maintenance should require the replacement of any component which forms part of an explosion- proof joint, only an original spare provided by BIFFI MUST be used. Direct repair or reconstruction of the above components are not permitted without the BIFFI permission.
Page 161
EN 13463-5: 2003 Terms and conditions Biffi Italia guarantees each single product to be free from defects and to conform to current goods specifications. Except when differently specified, the warranty period in one year from the date of installation by the first user, or eighteen months from the date of shipment to the first user, whichever occurs first.
Page 162
Normally the optional extension for additional entry/entries or additional electronic card are directly mounted on the base ICON2000/ICON2000AD by BIFFI and leaves the factory in perfect condition. Under this condition the general storage procedure as stated on the base INSTRUCTION HANDBOOK MAN 618 must be applied.
Page 168
60079-1 Standard. In case the maintenance should require the replacement of any component which forms part of an explosion-proof joint, only an original spare provided by BIFFI MUST be used. Direct repair or reconstruction of the above components are not permitted...
Page 176
EN 13463-5: 2003 Terms and conditions Biffi Italia guarantees each single product to be free from defects and to conform to current goods specifications. Except when differently specified, the warranty period in one year from the date of installation by the first user, or eighteen months from the date of shipment to the first user, whichever occurs first.
Page 177
Normally the optional extension for additional entry/entries or additional electronic card are directly mounted on the base ICON2000/ICON2000AD by BIFFI and leaves the factory in perfect condition. Under this condition the general storage procedure as stated on the base INSTRUCTION HANDBOOK MAN 618 must be applied.
Page 183
60079-1 Standard. In case the maintenance should require the replacement of any component which forms part of an explosion-proof joint, only an original spare provided by BIFFI MUST be used. Direct repair or reconstruction of the above components are not permitted...
Page 191
EN 13463-5: 2003 Terms and conditions Biffi Italia guarantees each single product to be free from defects and to conform to current goods specifications. Except when differently specified, the warranty period in one year from the date of installation by the first user, or eighteen months from the date of shipment to the first user, whichever occurs first.
Page 192
Normally the optional extension for additional entry/entries or additional electronic card are directly mounted on the base ICON2000/ICON2000AD by BIFFI and leaves the factory in perfect condition. Under this condition the general storage procedure as stated on the base INSTRUCTION HANDBOOK MAN 618 must be applied.
Page 198
60079-1 Standard. In case the maintenance should require the replacement of any component which forms part of an explosion-proof joint, only an original spare provided by BIFFI MUST be used. Direct repair or reconstruction of the above components are not permitted...
Page 210
Enclosure for Electrical Equipment Terms and conditions Biffi Italia guarantees each single product to be free from defects and to conform to current goods specifications. Except when differently specified, the warranty period in one year from the date of installation by the first user, or eighteen months from the date of shipment to the first user, whichever occurs first.
Page 211
Normally the optional extension for additional entry/entries or additional electronic card are directly mounted on the base ICON2000/ICON2000AD by BIFFI and leaves the factory in perfect condition. Under this condition the general storage procedure as stated on the base INSTRUCTION HANDBOOK MAN 618 must be applied.
Page 218
IEC (article 505 gas and 506 for dusts). The Class & Division system is used predominately in the United States, whereas the rest of the world generally uses the Zone system, and the BIFFI Electric Valve Actuator ICON2000 is approved and marked according the Class & Division System.
ICON2000v4_DPV1 is designed to support PROFIBUS redundant communication by installing two electronic modules on the same BIFFI electrical actuator ICON 2000v4. Operation and storage The module is designed to work and to be stored in the same environment of the actuator.
10 byte String ## if the char ‘decimal point’ (ASCII 0x2e) appears in the Software revision string the actuator is a BIFFI ICON2000; if the char ‘comma’ (ASCII 0x2c) appears the actuator is a BIFFI F01 2000 the Software revision string is made up of the base software revision and PROFIBUS interface revision with this format SW rev base (4 byte) –...
Page 269
Icon 2000 v4 Profibus EDD for AMS Manual INDEX THE EDDL TECHNOLOGY ICON 2000V4 PROFIBUS EDD FOR AMS INSTALLATION EDD Installation EDD Configuration CONFIGURE/SETUP Overview Name Plate Valve Data Maintenance commands 4.4.1 Set Device Date and Time DEVICE DIAGNOSTICS Actuator Status...
Page 270
Icon 2000 v4 Profibus EDD for AMS Manual The EDDL Technology The Electronic Device Description Language (EDDL) is a text-based language that may be used to describe the characteristics of field devices. It is very similar to HTML web pages concept. There’s an EDDL text file that tells which commands to send to request data, how to decode answers from the filed device and how to display data on the user interface.
Page 271
Icon 2000 v4 Profibus EDD for AMS Manual Icon 2000v4 Profibus EDD for AMS This EDD, developed by Biffi, provides to customers an easier access to Icon 2000v4 actuator parameters via Profibus DP-V1 interface. It is designed and tested for AMS Device Manager Version 12.5.000.118, under Windows 7 Operating System.
Page 272
Icon 2000 v4 Profibus EDD for AMS Manual Installation EDD Installation Installation of the EDD provided by Biffi Italia, must be done following the procedure below: Select “Add Device Type” into the “AMS Device Manager” program group. 2. A Warning message will be displayed.
Page 273
Icon 2000 v4 Profibus EDD for AMS Manual The installation progress bar will be displayed: 5. A termination message will be displayed at the end of the installation. Select “Ok” button to terminate. EDD Configuration When an ICON 2000v4 is connected to the profibus network, the actuator will be shown into the “AMS Device Manager”...
Page 274
Icon 2000 v4 Profibus EDD for AMS Manual 2. A new window will be displayed. Select the “Identify Device” button. 3. Once identified, the window will be updated with device data. Select “Close” button to terminate. The actuator will be displayed into the “AMS Device Manager” application as it is shown on the figure...
Page 275
Icon 2000 v4 Profibus EDD for AMS Manual Configure/Setup Overview This is the first page shown when a double click with the mouse is done on the actuator into the AMS interface, and displays the more significant status information. All the displayed data are READ-ONLY and dynamically updated.
Page 276
Icon 2000 v4 Profibus EDD for AMS Manual Name Plate This page displays information about the actuator Name Plate. All the displayed data are READ-ONLY and static: the data are read from the actuator only when the window is opened.
Page 278
Icon 2000 v4 Profibus EDD for AMS Manual Maintenance commands Into this page are grouped maintenance operations that can be done on the Icon 2000v4 actuator. All the displayed data can be modified; the data are read from the actuator when the window is opened: a ‘Refresh’...
Page 279
Icon 2000 v4 Profibus EDD for AMS Manual 4.4.1 Set Device Date and Time By means of this window the current date and time can be sent to the Icon 2000v4 actuator. Name Description Set Current Date Entry filed for define the current date...
Page 280
Icon 2000 v4 Profibus EDD for AMS Manual Device Diagnostics Actuator Status Critical actuator states that can stop the functioning of the actuator are highlighted in this page. All the displayed states are READ-ONLY and dynamically updated. Name Description Alarm...
Page 281
Icon 2000 v4 Profibus EDD for AMS Manual Maintenance Information / Alarms Log The Alarms Log Tab, shows the last 5 alarms occurred on Icon 2000 v4 actuator. The Alarm #1 is the more recent and the Alarm #5 is the oldest.
Page 282
Icon 2000 v4 Profibus EDD for AMS Manual Maintenance Information / Warnings Log The Warnings Log Tab, shows the last 5 warnings occurred on Icon 2000 v4 actuator. The Warning #1 is the more recent and the Warning #5 is the oldest.
Page 283
Icon 2000 v4 Profibus EDD for AMS Manual Maintenance Information / Torque profile The Torque profile Tab, collect the information about the Icon 2000 v4 torque profile. All the displayed data are READ-ONLY and static. The data are read from the actuator only when the window is opened: a ‘Refresh’...
Page 284
It is possible to set reference data dates from “Configure/Setup - Maintenance Commands” page. Maintenance Information / Operation Log This Tab collects the Operation log information of icon 2000 v4 Actuator. All the displayed data are READ-ONLY and static. The data are read from the actuator only when the window is opened: a ‘Refresh’...
Page 285
Icon 2000 v4 Profibus EDD for AMS Manual The page is divided in two areas; one for the “General Maintenance Information”, the other for the “Recent Maintenance Information”. The displayed data are: Name Description Contactor cycles Count of the cycles of contactors K1 and K2...
Page 286
Icon 2000 v4 Profibus EDD for AMS Manual Maintenance Information / Maintenance dates This Tab collects the dates of important actuator services. All the displayed data are READ-ONLY and static. The data are read from the actuator only when the window is opened: a ‘Refresh’...
Page 287
Icon 2000 v4 Profibus EDD for AMS Manual Process Variables Actuator Status The complete list of the states of the actuator is displayed into this page. All the displayed states are READ-ONLY and dynamically updated. The followings data are displayed:...
Page 288
Icon 2000 v4 Profibus EDD for AMS Manual Name Description din 1 Status of configurable DIN1 condition din 2 Status of configurable DIN2 condition din 3 Status of configurable DIN6 condition din 4 Status of configurable DIN4 condition din 5...
Page 290
Trends Torque & Position This window shows in a single graph the trend curve of torque and position of Icon 2000 v4 actuator. Using buttons positioned over the graph, operations like zoom, scroll and return to the standard display can be done.
Need help?