Download Print this page

Bosch FMR-1000-RA Quick Start Manual page 2

Fire alarm systems remote annunciator

Advertisement

2 | FMR‑1000‑RA Remote Annunciator
Installation/Configuration Notes
Mounting Considerations
The Remote Annunciator can be surface mounted in the
supplied back box or flush mounted using a 3‑gang
electrical box.
Note
The annunciator should be mounted no higher
than shoulder height of the shortest person
operating the system.
Wiring Considerations
Use four conductor, 18 AWG (0.8 mm
connect the Remote Annunciator to the Option Bus of the
FACP. The total length of wire connected to the Option Bus
terminals must not exceed 4000 ft (1219 m), regardless of
the wire gauge used. Refer to FPA‑1000‑UL Installation and
Operation Guide (F01U075420) for detailed wire length
calculations.
Parts Included
Quant.
Component
1
Remote annunciator in back box with cover frame
Tabs with different language versions for LED and key text
1
Hardware pack
1
Literature – Installation and Operation Guide
Technical Specifications
Electrical
Voltage (operating):
12 VDC or 24 VDC nominal
Current consumption at 12 VDC
Alarm:
150 mA maximum (with annunciator lighted and
piezo sounder on)
Stand-by:
25 mA maximum (only Power LED on)
Current consumption at 24 VDC
Alarm:
120 mA maximum (with annunciator lighted and
piezo sounder on)
Stand-by:
30 mA maximum (only Power LED on)
Americas:
Europe, Middle East, Africa:
Bosch Security Systems, Inc.
Bosch Security Systems B.V.
130 Perinton Parkway
P.O. Box 80002
Fairport, New York, 14450, USA
5600 JB Eindhoven, The Netherlands
Phone: +1 800 289 0096
Phone: + 31 40 2577 284
Fax: +1 585 223 9180
Fax: +31 40 2577 330
security.sales@us.bosch.com
emea.securitysystems@bosch.com
www.boschsecurity.us
www.boschsecurity.com
© Bosch Security Systems Inc. 2009 | Data subject to change without notice
T5691240971 | Cur: en-US, V3, 27 Oct 2009
2
) or larger wire to
Asia-Pacific:
Robert Bosch (SEA) Pte Ltd, Security Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6258 5511
Fax: +65 6319 3499
apr.securitysystems@bosch.com
www.boschsecurity.com
Environmental
Environment:
Environment Friendly:
Protection Class:
Relative Humidity:
Temperature (operating):
Temperature (storage):
Mechanical
Operating and Display Elements
LCD:
4‑line x 20‑character display, backlit
LEDs:
Six: Fire Alarm (red); Gas Alarm (blue); Power
(green); Supervisory, Silenced, and Trouble
(3 x yellow)
Keys:
Acknowledge key, 4 navigation keys
Sounder:
Built-in piezo sounder
Housing
Material:
ABS-FR
Color:
Red
Dimensions (W x H x D)
7.40 in x 4.41 in x 1.89 in.
Back box:
(188 mm x 112 mm x 48 mm)
Cover frame:
7.40 in x 4.41 in x 2.40 in.
(188 mm x 112 mm x 61 mm)
Weight:
15.2 oz (430 g)
Wiring
Cable Entries:
3 knockouts for ½ in. diameter conduit con-
nectors on back, bottom and top side
Connections:
4 terminals
Wre Gauge:
12 AWG to 18 AWG
(0.75 mm
Wire Type:
Non-shielded, four conductor wire
Ordering Information
FMR‑1000‑RA Remote Annunciator
LCD annunciator without system control capa-
bility for use with the FPA‑1000‑UL Compact
Fire Panel
Represented by
Indoor, dry
RoHS compliant
IP 30 (per IEC 605029)
Up to 95%, non‑condensing
+32°F to +120°F (0°C to +49°C)
-4°F to +140°F (-20°C to +60°C)
2