Sinclair SCV EB Series Installation And User Manual page 32

Air-cooled modular chiller unit
Table of Contents

Advertisement

2) Applicable standard of water quality for the unit
Table 8-9
PH value
Total hardness
Conductivity
Sulfide ion
Chloride ion
Ammonia ion
8.6.9 Installation of multi-module water system pipeline
Multi-module combination installation involves special design of the unit, so relevant explanation is given as follows.
1) Installation mode of multi-module combination water system pipeline
No.n module
No. (n-1)address
Pump
Fig.8-24 Installation of multi-module (no more than 16 modules)
2) Table of diameter parameters of main inlet and outlet pipes
Table 8-10
Cooling capacity
15≤Q≤30
30<Q≤90
90<Q≤130
130<Q≤210
210<Q≤325
325<Q≤510
510<Q≤740
740<Q≤1300
1300<Q≤2080
Please pay attention to the following items when installing multiple modules:
- Each module corresponds to an address code which cannot be repeated.
- Main water outlet temperature sensing bulb, target flow controller and auxiliary electric heater are under control of
the main module.
- One wired controller and one target flow controller are required and connected on the main module.
- The unit can be started up through the wired controller only after all addresses are set and the aforementioned
items are determined. The wired controller is ≤500m away from the outdoor unit.
6.8~8.0
<70ppm
<200μV/cm(25°C)
No
<50ppm
No
No.(n-1) module
No.(n-2) address
Total inlet and outlet water pipe inside nominal diameter
CAUTION
27
Sulfate
<50ppm
Silicon
<30ppm
Iron content
<0.3ppm
Sodium ion
No requirement
Calcium ion
<50ppm
/
No.1 module
No.0 address
Drill dead hole at the position,
and move the total euent
temperature sensor at No.0
address to the position
DN40
DN50
DN65
DN80
DN100
DN125
DN150
DN200
DN250
/