Npn discrete input & npn transistor output module, 8 points each (modbus 115.2 kbps)

Advertisement

MODBUS FUNCTION CODES & SUPPORTED CODES
■ Data and Control Functions
CODE
NAME
01
Read Coil Status
02
Read Input Status
03
Read Holding Registers
04
Read Input Registers
05
Force Single Coil
06
Preset Single Register
08
Diagnostics
11
Fetch Comm. Event Counter
12
Fetch Comm. Event Log
15
Force Multiple Coils
16
Preset Multiple Registers
17
Report Slave ID
■ Exception Codes
CODE
NAME
01
Illegal Function
02
Illegal Data Address
03
Illegal Data Value
■ Diagnostic Subfunctions
CODE
NAME
00
Return Query Data
MODBUS I/O ASSIGNMENT
ADDRESS
Coil (0X)
17 – 32
Inputs (1X)
17 – 32
33 – 48
49 – 64
65 – 80
Input Registers (3X)
17 – 24
25 – 48
Holding Registers (4X)
17 – 20
21 – 48
I: Integer, -1500 – +11500 (-15 – +115%)
F: Floating
Note: DO NOT access addresses other than mentioned above. Such access may cause problems such as inadequate operation.
Digital output from the slave (read/write)
Status of digital inputs to the slave (read only)
General purpose register within the slave (read/write)
Collected data from the field by the slave (read only)
Digital output from the slave (read/write)
General purpose register within the slave (read/write)
Fetch a status word and an event counter
A status word, an event counter, a message count and a field of event bytes
Digital output from the slave (read/write)
General purpose register within the slave (read/write)
Slave type/ 'RUN' status
Function code is not allowable for the slave
Address is not available within the slave
Data is not valid for the function
Loop back test
DATA TYPE
DATA
1 – 16
Digital Output (discrete output of the basic module)
Digital Output (discrete output of the extension module)
1 – 16
Digital Input (discrete input of the basic module)
Digital Input (discrete input of the extension module)
Reserved (unused)
Module Status
Reserved (unused)
1 – 4
I
Analog Input
5 – 16
----
Reserved (unused)
F
Analog Input
----
Reserved (unused)
1 – 2
I
Analog Output
3 – 16
----
Reserved (unused)
F
Analog Output
----
Reserved (unused)
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
R7M-DAC16C
EM-7803-AK Rev.4 P. 7 / 8