External Dimensions; Connection Diagram; Wiring Instructions - M-system R7M-CT4E Instruction Manual

Ac current input module, 4 points (modbus; clamp-on current sensor clse use)

Advertisement

EXTERNAL DIMENSIONS

4
5
6
7
1
2
3

CONNECTION DIAGRAM

Connect the unit as in the diagram below.
INPUT 0
10
K0
11
L0
INPUT 1
12
K1
13
L1
INPUT 2
15
K2
16
L2
INPUT 3
17
K3
18
L3
In order to improve EMC performance, bond the FG
terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.
Input Connection Example
SOURCE
k
CLAMP-ON SENSOR
l
LOAD
unit: mm (inch)
115 (4.53)
10 11 12 13
14
15 16 17 18
1
2
3
4
5
6
7
6 (.24)
7–M3 SCREW
18–M3 SCREW
TERMINALS
for Modbus, POWER
4
DA
1
DB
5
DG
2
SLD
3
FG
6
24VDC
7
0V
Kn
Ln
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: + 81 ( 6 ) 6659-8201 Fax: + 81 ( 6 ) 6659-8510 E-mail: info@m-system.co.jp
17 (.66)
9
8
6 (.24)
TERMINALS
for INPUT

WIRING INSTRUCTIONS

■ SCREW TERMINAL
Torque: 0.5 N·m
■ SOLDERLESS TERMINAL mm (inch)
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable. Solder-
less terminals with insulation sleeve do not fit.
Communication cable: Applicable wire size 0.2 to 0.5 mm
(AWG26 - 22)
Recommended manufacturer: Japan Solderless Terminal
MFG.Co.Ltd
Others: 0.25 to 1.65 mm
Recommended manufacturer: Japan Solderless Terminal
MFG.Co.Ltd, Nichifu Co.,ltd
R7M-CT4E
54 (2.13)
DIN RAIL
35mm wide
30 (1.18)
[5 (.20)]
(AWG 22 to 16)
2
3.3 (.13) max
mm (inch)
EM-7803-R Rev.3
2
P. 3 / 7