Page 1
INSTALLATION MANUAL APPLICATION The TE80SB Thermostat provides universal replacement of single-stage, 24Vac (20 mA to 1.5A) thermostats used in electric, gas, and oil heating and cooling systems. This thermostat is mercury free and requires no batteries. The thermostat also can be used to control single stage heat pumps.
Vtronix SPECIFICATIONS Table 2. Thermostat specifications. Power Power Supply 24 Vac nominal, 18-30 Vac, 50/60 HZ. Electrical Rating Heating rating 0.02 to 1.5 A continuous Cooling rating 0.02 to 1.5 A continuous Fan rating 0.02 to 0.5 A continuous Note: The fan load plus the higher of the heating or cooling load must not exceed 1.5 Amp continuous...
Vtronix Using back plate as a guide, mark two mounting INSTALLATION holes on the wall. Drill two mounting holes. Place Read these instructions thoroughly before installing anchors (provided) into the holes until flush with product. Failure to follow these instructions could the hole.
Page 4
Vtronix HEAT PUMP WITH Set-up switch (E/F) HEAT ACTIVE REVERSING VALVE WARNING Fire Hazard. Failure to set the set-up switch to the E position when electric resistance heat is used may result in the overheating of the electric heater elements due to improper fan operation.
Vtronix Secure the thermostat by tightening the screw Testing Heating / Cooling Equipment. (OP:01) provided to protect the thermostat from unwanted While in the installer setup, slide the mode switch to access. heat to operate the heating equipment or cool to operate the cooling equipment.
Page 6
Vtronix Setting Heating Cycle Rate. (OP:03) ∇ b. Press key to change algorithm. In cooling, the cycle rate is fixed at 4 Cycles per 0 = Normal algorithm (default). hour. To set the cycle rate in heating; while in 1 = Aggressive algorithm.
Vtronix Time format. (OP:07) OPERATION The clock on the display can be selected to show System Setting either 24-hour or AM/PM format. While in the Use mode switch for selecting system operation. installer setup, Cool : The thermostat controls the cooling a.
Page 8
Vtronix Press ‘PROG’ and select set point PROGRAMMING SCHEDULE ∆ ∇ by pressing key. Select system switch in heat or cool mode. Heat or Cool depends on system Press “PROG” to enter program mode. Display switch selection. If system switch will prompt to select day.
Vtronix ADJUSTING TEMPERATURE CLOCK ADJUSTMENT Adjusting the temperature during any program will The clock needs to be adjusted when installed. The make the thermostat to temporarily use this set clock will be retained for a few hours in case of point until the next program.
Vtronix SYSTEM CHECKOUT Cooling Checkout WARNING ! Do not operate in cooling mode when the outdoor temperature is below 50 °F ( 10 °C) otherwise the compressor might be damaged. 1. Slide mode switch to COOL, O terminal will get energized.
Need help?
Do you have a question about the TE80SB and is the answer not in the manual?
Questions and answers