Technical Manual for the Sounders DB5
www.acornfiresecurity.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PX805002 and is the answer not in the manual?

Questions and answers

Summary of Contents for MEDC PX805002

  • Page 1 www.acornfiresecurity.com Technical Manual for the Sounders DB5 Please note that every care has been taken to ensure the accuracy of our technical manual. We do not, however, accept responsibility for damage, loss or expense resulting from any error or omission. We reserve the right to make alterations in line with technical advances and industry standards.
  • Page 2 01/17 © MEDC 2017 www.acornfiresecurity.com...
  • Page 3 (ATEX 12Vdc only) 2.0 INSTALLATION The sounder should be positioned using the two of the available fixing holes in the base. MEDC recommend that stainless steel nuts and bolts be used, if the environment is corrosive. The sounder will operate in any attitude - from horizontal to vertical. However, it is important to note that the alignment of the Sounder should ensure that:- Dust or debris cannot lodge or settle in the cover apertures.
  • Page 4 2.3 Wiring Details 01/17 © MEDC 2017 www.acornfiresecurity.com...
  • Page 5 Note – The DB5 sounder has internal resistance that limits the input current to a nominal 28mA when connected to a 28V source. With an Ii of 150mA and In=28mA, this allows five (5) DB5 sounders to be connected in Parallel. © MEDC 2017 01/17 www.acornfiresecurity.com...
  • Page 6 During the working life of the sounder, it should require little or no maintenance. However, if abnormal or unusual environmental conditions occur due to plant damage or accident etc., then visual inspection is recommended. The product cannot be repaired by the user and must be replaced by an identical unit. 01/17 © MEDC 2017 www.acornfiresecurity.com...
  • Page 7 The ATEX certificate and the product label carry the ATEX group and category marking: I M1 Where signifies compliance with ATEX. Signifies suitability for use in underground mining industries. the product is intended to remain energised in the event of an explosive atmosphere Signifies © MEDC 2017 01/17 www.acornfiresecurity.com...