Installing the equipment interface module (EIM)
NOTE:
If an EIM is mounted inside a metal cabinet, it is recommended to use
a THM4000R1000 Wireless Adapter for extended wireless range. Mount the
Wireless Adapter outside the metal cabinet and connect to the ABCD terminals at
the EIM.
NOTE:
When installing multiple
thermostats and EIMs, mount the
EIMs at least 2 feet apart for best
RedLINK performance.
1.1 Mount EIM.
Mount the EIM near the HVAC
equipment or on the equipment
itself.
Use screws and anchors as
appropriate for the mounting
surface.
1.2 Wire EIM as shown.
Refer to the table and wiring diagrams on pages 3-5.
NOTE:
If you are installing discharge and return air sensors, refer to the mounting
instructions in the Alerts and Delta T Diagnostics Installation Instructions packed
in the kit.
Conventional System
Terminal
Common wire from 24 VAC
C
transformer.
Power wire from 24 VAC
R*
transformer.
RH*
Heating power.
RC*
Cooling power.
W
Heat Stage 1
W2
Heat Stage 2
W3
Heat Stage 3
Y
Compressor Stage 1
Y2
Compressor Stage 2
G
Fan Relay
Connect to Economizer Module or
A
Lighting Panel (TOD).
*
Remove jumpers when separate transformers are used.
69-2739_A.indd 3
Terminal Designations
Description
Heat Pump
Terminal
Common wire from 24 VAC
C
transformer.
Power wire from 24 VAC
R
transformer.
RH
Heating power.
RC
Cooling power.
O/B
Changeover valve for heat pumps.
Backup Heat Stage 1/Emergency
AUX 1
Heat Stage 1
Backup Heat Stage 2/Emergency
AUX 2
Heat Stage 2
Y
Compressor Stage 1
Y2
Compressor Stage 2
G
Fan Relay
Connect to Compressor Monitor,
L/A
Zone Panel, Economizer Module or
Lighting Panel (TOD).