Download Print this page

Status Config Menu - Siemens Argus 8 7SG11 Manual

Voltage and frequency relays

Advertisement

SETTING
Gn Status ..n
sets the output relay(s) operated by Status Input n
energisation
Gn Trip counter Alarm
sets the output relay(s) operated by the Trip
Counter Alarm function
Gn PowerOn Count
sets the output relay(s) operated by the Power On
Count Alarm function
Gn Hand Reset
sets the output relay(s) which are to stay latched
after operation. These can be reset via the fascia, a
status input, or a communications command
Min O/P Energise Time
sets the minimum output pulse length of energised
output relays

9 Status Config Menu

SETTING
Settings Group Select
sets the status input(s) required to select a settings
group to become the active settings group. Note
that the lower the number of status input, the higher
precedence that it has e.g. Status 1 will take
precedence over all the rest
Inverted Inputs
sets the status input(s) required to be inverted. Any
function assigned to an inverted input becomes
active when the input is de-energised
Gn VE1 Inhibit
sets the status input(s) which will inhibit Voltage
Element 1
Gn VE2 Inhibit
Gn VE3 Inhibit
Gn VE4 Inhibit
Gn 3VoE1 Inhibit
Gn 3VoE2 Inhibit
Gn V2E1 Inhibit
Gn V2E2 Inhibit
Gn FE1 Inhibit
Gn FE2 Inhibit
Gn FE3 Inhibit
Gn FE4 Inhibit
Gn Trip Circuit Fail
sets the status input(s) which will be used within the
Trip Circuit Monitoring scheme
Gn ALARM 1
sets the status input(s) which, on energisation, will
cause the Alarm 1 message to be displayed on the
LCD
Gn ALARM ..n
Gn Waveform Trigger
sets the status input(s) which, on energisation, will
cause a waveform record to be stored
©2010 Siemens Protection Devices Limited
7SG11 Argus 8 Relay Settings
RANGE
RL1..RLn
RL1..RLn
RL1..RLn
RL1..RLn
100 – 500ms step 50ms
RANGE
S1..Sn
(each status can be set from 1-8 to
select active group 1-8)
S1..Sn
S1..Sn
S1..Sn
S1..Sn
S1..Sn
S1..Sn
S1..Sn
S1..Sn
S1..Sn
S1..Sn
S1..Sn
S1..Sn
S1..Sn
S1..Sn
S1..Sn
S1..Sn
S1..Sn
Chapter 3 Page 8 of 10
DEFAULT
None
None
None
None
100ms
DEFAULT
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None
None

Advertisement