ROOF TERMINATED
EXHAUST PIPE
SIDE WALL
TERMINATED
FURNACE
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE : Each opening shall have a free area of at least one square inch
2
per 1,000 Btu (645 mm
per .29 kW) per hour of the total input rating of
all equipment in the enclosure, but not less than 100 square inches
2
(64516 mm
).
Figure 4. Equipment in Confined Space - All Air from
Air from Outside
If air from outside is brought in for combustion and
ventilation, the confined space shall be provided with two
permanent openings. One opening shall be within 12" (305
mm) of the top of the enclosure and one within 12" (305 mm)
of the bottom. These openings must communicate directly
or by ducts with the outdoors or spaces (crawl or attic) that
freely communicate with the outdoors or indirectly through
vertical ducts. Each opening shall have a minimum free
area of 1 square inch per 4,000 Btu (645 mm² per .59 kW)
per hour of the total input rating of all equipment in the
enclosure (see Figure 5 and Figure 6). It is also permissible
to bring air for combustion from a ventilated attic (Figure 8)
or ventilated crawl space (Figure 9).
(Inlet Air from Crawl Space and Outlet Air to Ventilated Attic)
ROOF TERMINATED
EXHAUST PIPE
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE: The inlet and outlet air openings shall each have a free area
of at least one square inch per 4,000 Btu (645 mm
hour of the total input rating of all equipment in the enclosure.
Figure 5. Equipment in Confined Space - All Air from
Page 8 of 53
OPENINGS
(To Adjacent
Uncon ned
Space)
Inside
VENTILATION LOUVERS
(Each end of attic)
OUTLET
AIR
FURNACE
VENTILATION
LOUVERS
INLET
(For unheated
AIR
crawl space)
2
per 1.17 kW) per
Outside
When communicating with the outdoors through horizontal
ducts, each opening shall have a minimum free area of 1
square inch (645 mm²) per 2,000 Btu (.56 kW) per hour of
the total input rating of all equipment in the enclosure. See
Figure 7.
When ducts are used, they shall be of the same cross-
sectional area as the free area of the openings to which
they connect. The minimum dimension of rectangular
air ducts shall be no less than 3 inches (75 mm). In
calculating free area, the blocking effect of louvers, grilles,
or screens must be considered. If the design and free area
of protective covering is not known for calculating the size
opening required, it may be assumed that wood louvers
will have 20 to 25 percent free area and metal louvers and
grilles will have 60 to 75 percent free area. Louvers and
grilles must be fixed in the open position or interlocked
with the equipment so that they are opened automatically
during equipment operation.
(All Air Through Ventilated Attic)
ROOF TERMINATED
EXHAUST PIPE
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE: The inlet and outlet air openings shall each have a free area of
at least one square inch per 4,000 Btu (645 mm
of the total input rating of all equipment in the enclosure.
Figure 6. Equipment in Confined Space - All Air from
ROOF TERMINATED
EXHAUST PIPE
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE: Each air duct opening shall have a free area of at least one
square inch per 2,000 Btu (645 mm
input rating of all equipment in the enclosure. If the equipment room
is located against an outside wall and the air openings communi-
cate directly with the outdoors, each opening shall have a free area
of at least 1 square inch per 4,000 Btu (645 mm
hour of the total input rating of all other equipment in the enclosure.
Figure 7. Equipment in Confined Space - all Air from
Issue 1933
VENTILATION LOUVERS
(Each end of attic)
OUTLET
AIR
INLET AIR
FURNACE
(Ends 12" above
bottom)
2
per 1.17 kW) per hour
Outside
OUTLET AIR
FURNACE
INLET AIR
2
per .59 kW) per hour of the total
2
per 1.17 kW) per
Outside