COMFORT-AIRE Century GDD95C Installation Instructions Manual page 26

Warm air gas furnace downflow air discharge
Hide thumbs Also See for Century GDD95C:
Table of Contents

Advertisement

Details of Exhaust Piping Terminations for Non-
Direct Vent Applications
Exhaust pipe may be routed either horizontally through
an outside wall or vertically through the roof. In attic or
closet installations, vertical termination through the roof
is preferred. Figure 38 through Figure 41 show typical
terminations.
1.
Exhaust piping must terminate straight out or up as
shown. The termination pipe must be sized as listed
in Table 7. The specified pipe size ensures proper
velocity required to move the exhaust gases away
from the building.
2.
On field supplied terminations for side wall exit,
exhaust piping may extend a maximum of 12 inches
(305 mm) for 2" PVC and 20" (508 mm) for 3" (76 mm)
PVC beyond the outside wall. See Figure 39.
3.
If exhaust piping must be run up a sidewall to position
above snow accumulation or other obstructions, piping
must be supported every 24" (610 mm) as shown in
Figure 40. When exhaust piping must be run up an
outside wall, any reduction in exhaust pipe size must
be done after the final elbow.
12" (305MM)
ABOVE AVE.
SNOW
ACCUMULATION
3" (76MM) OR
2" (51MM) PVC
PROVIDE SUPPORT
FOR EXHAUST LINES
Figure 38. Non-Direct Vent Roof Termination Kit
(15F75 or 44J41)
FIELD-PROVIDED
REDUCER MAY BE
REQUIRED TO
ADAPT DIFFERENT
VENT PIPE SIZE TO
TERMINATION
SIZE TERMINATION
PER EXHAUST PIPE
TERMINATION SIZE
REDUCTION TABLE
Figure 39. Non-Direct Vent Field Supplied Wall
Termination
Page 26 of 53
SIZE PER EXHAUST PIPE
TERMINATION SIZE
REDUCTION TABLE
UNCONDITIONED
ATTIC SPACE
Issue 1933
FIELD-PROVIDED
REDUCER MAY BE
REQUIRED TO
ADAPT DIFFERENT
VENT PIPE SIZE TO
TERMINATION
* Use wall support every 24" (610 mm). Use two supports of extension is greater than 24"
(610 mm) but less than 48" (1219 mm).
Figure 40. Non-Direct Vent Field Supplied Wall
Termination Extended
Minimum 12" (305MM)
above chimney top
plate or average snow
accumulation
SHEET
METAL TOP
PLATE
INSULATE
TO FORM
SEAL
* SIZE TERMINATION PIPE
PER EXHAUST PIPE TERMINATION
SIZE REDUCTION TABLE
NOTE − Do not discharge exhaust gases directly into any chimney
or vent stack. If vertical discharge through an existing unused
chimney or stack is required, insert piping inside chimney until the
pipe open end is above top of chimney and terminate as illustrated.
In any exterior portion of chimney, the exhaust vent must be
insulated.
Figure 41. Non-Direct Vent Application Using Existing
Chimney
SIZE TERMINATION
PER EXHAUST PIPE
TERMINATION SIZE
REDUCTION TABLE
STRAIGHT-CUT OR
ANGLE-CUT IN DIRECTION
OF ROOF SLOPE
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
EXTERIOR
PORTION OF
CHIMNEY
507735-03

Advertisement

Table of Contents
loading

Table of Contents