Local Loop" - Local Console Fault; Lo Z" - Line Fault - Local Console Fault; Hi Z" - Line Fault - Local Console Fault; Nw Audio Loop" - Network Audio Fault - Baldwin Boxall C2CFPE Installation Instructions Manual

Table of Contents

Advertisement

Care2
Installation Instructions

7.7.4 "Local Loop" - Local Console Fault

7.7.5 "Lo Z" - Line Fault - Local Console Fault

7.7.6 "Hi Z" - Line Fault - Local Console Fault

7.7.7 "NW Audio Loop" - Network Audio Fault

7.7.8 "NW Loop" - Network Data Fault

7.7.9 Deep Discharge (Low Voltage) Protection

82
www.acornfiresecurity.com
The Front Panel cannot detect the correct number of internal
devices (C2CK4 Line Cards & C2CN Network Cards) to match
the stored configuration.
The console has detected the Line Impedance has dropped below
the minimum threshold (potentially a Short Circuit).
The console has detected the Line Impedance has increased
beyond the maximum threshold (potentially an Open Circuit).
An Audio Fault has been detected on the network or the Audio
Network Loop is no longer intact due to an open or short circuit.
A Data Fault has been detected on the network or the Data
Network Loop is no longer intact due to an open or short circuit.
The Internal Power Supply will disconnect the batteries if they
discharge below 21V.
www.acornfiresecurity.com