Portable actuator for remotely operating certain ite k breakers

Advertisement

STEP #2
Rotate the magnet levers
inward so that the magnets are retracted.
(shown by RED arrows)
STEP #3
Align the actuator on the top
of the breaker (shown by BLUE arrows)
STEP #4
While continuing to hold the
actuator frame against the top edge of the
breaker, flip the magnet levers (shown by
RED arrows) so the magnets engage the
switchgear door. NOTE: The actuator frame
must be against the top breaker edge or the
actuator plungers will not align properly with
the breaker TRIP and CLOSE buttons.