Free Access Underfloor Connection Of Power Cable; Cutoff Characteristics Of Distribution Panel (At The Time Of Connecting Power Distribution Box) - Cisco C880 Hardware Installation Manual

Hide thumbs Also See for C880:
Table of Contents

Advertisement

2.4

Free Access Underfloor Connection of Power Cable

If the height of underfloor is less than 300mm (11.8 in.), the power distribution is set to sideways.
FIGURE 2.12 When Underfloor Height is less than 300mm (11.8 in)
The connector format and cable bend radius of power cable are considered at the time of connecting the
power cable of power distribution box (or base cabinet) under the free access floor. It is recommended that
the under floor height is 300 mm (11.8 in) or more.
The recipient power distribution should be arranged near the device.
FIGURE 2.13 When the under floor height is 300 mm (11.8 in) or more.
Remarks
The above figure shows an example of 19-inch rack mounted with the device.
2.5
Cutoff Characteristics of Distribution Panel (At the time
of connecting power distribution box)
At the time of connecting the distribution panel through power distribution box, protection should be
coordinated so that the breaker of the device (or power distribution box) trips before the breaker of the
distribution panel trips. Such protection should be maintained. Therefore, the distribution panel should have
the characteristic conditions shown in
It is necessary to use Distribution panel Breaker suitable to these conditions.
Number
(1)
Free access floor
(2)
Less than 300mm (11.8 in)
(3)
Recipient power distribution
Number
(1)
Free access floor
(2)
200 mm (9.8 in)
(3)
300 mm (11.8 in) or more
(4)
Recipient power distribution
"TABLE 2.3 Characteristic Condition of Distribution Panel
Description
Description
18
Breaker".

Advertisement

Table of Contents
loading

This manual is also suitable for:

C880e7-8800 v2C880 e7-8800 v3C880 e7-8800 v4

Table of Contents