Csc-5S; System; Signal - Hitachi SAMURAI Series Manual

Hide thumbs Also See for SAMURAI Series:
Table of Contents

Advertisement

6.7.CSC-5S

CSC-5S is a remote controller for Hitachi Water Chillers

6.7.1. System

CSC-5S allows the individual control of a Chiller Unit as well as it allows a centralized and grouped controls
of a maximum number of 8 chillers.

CSC-5S

6.7.2. Signal

Indication code
ON/OFF unit operation
Setting Temperature COOL
Setting Temperature HEAT
Operation Mode
C1Pd ~ C2Pd
Discharge Pressure
C1Ps ~ C2Ps
Suction Pressure
C1td ~ C2td
Discharge Gas Temperature
C1ts ~ C2ts
Suction Gas Temperature
C1tr ~ C2tr
Liquid Refrigerant Temperature
CEL
Inlet Water Temperature
CoL
Outlet Water Temperature
CcoL
Individual Water Piping Outlet Temperature
tSC
Setting Temperature of Chilled Water
tSH
Setting Temperature of Hot Water
tSCd
Setting Analog Temperature of Chilled Water
tSHd
Setting Analog Temperature of Hot Water
dF
Differential Setting
tA
Ambient Temperature
Crno
ROM No. of Chiller Unit
CvEr
Version No. of Chiller Unit
rno
ROM No. of Controller (CSC-5S)
TCGB0051 rev 0 - 09/2009
44
Indication Content
8 Chillers (Maximum)
Unit
Remark
°C
°C
MPa
MPa
Indicate Max. 6
°C
Refrigerant Circuit Data
°C
°C
°C
°C
The display contents
°C
depend on chiller unit.
°C
°C
°C
Not available
°C
Not available
°C
°C
Installation
Technical Catalogue
Control Monitoring
Control Data
Monitoring Data

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Samurai clg2

Table of Contents