Trane Axiom EXW Series Installation, Operation And Maintenance Manual page 28

Water source heat pump water-to-water
Table of Contents

Advertisement

Troubleshooting
Table 15. Troubleshooting checklist (continued)
Problem
High head pressure
Low suction pressure
Low Pressure switch open
Freezestat open
28
Heating Cooling Cause
X
Trash in heat exchanger
X
Low water flow
X
X
Overcharge of refrigerant
X
X
Non-condensable in system
X
X
Water too hot
X
X
Undercharged
X
X
Restricted thermal expansion valve
X
Inadequate GPM
X
Inadequate GPM
X
Water too cold
X
X
Undercharged with refrigerant
X
X
Defective pressure switch
X
X
Heat transfer fluid too cold
X
Inadequate GPM
X
Water too cold
X
X
Defective freezestat
X
Heat transfer fluid too cold
Correction
Backflush
Increase GPM
Decrease charge
Evacuate and recharge by weight
Decrease temperature
Locate leak, repair and recharge
Repair / replace
Increase GPM
Increase GPM
Increase temperature
Increase charge
Replace
Raise water temperature
Increase GPM
Increase GPM
Replace freezestat
Replace freezestat