Flow Checks
For the operating temperature drop (heating) and rise
(cooling), refer to Table 7 through Table 12 for the proper
water temperature change. Depending on the unit size
entering water temperature and water flow rate, the
cooling temperature rise is from 8°F-16°F. Based on the
same criteria for heating, the temperature drop is from
2°F-13°F.
Pressure
Using the P/T ports and one 0-60 psi pressure gauge with
the P/T port adapter, measure the pressure difference
between the water-in and water-out connections.
Compare the pressure differential to Table 7 through Table
12 to determine flow.
Job Name:
Model Number:
Date:
Serial Number:
Installing Contractor: Use this form to thoroughly check-
out the system and units before and during start-up. (This
form need not be returned to the factory unless requested
during technical service support).
MODE
Entering fluid temperature
Leaving fluid temperature
Temperature differential
Water coil heat exchanger (Water Pressure IN)
Water coil heat exchanger (Water Pressure OUT)
Pressure Differential
COMPRESSOR
Amps
Volts
Discharge line temperature (after 10 minutes)
WSHP-SVX02E-EN
Water Volume Cubic Inches
359.6
719.2
2079.0
Water Volume Cubic Feet
0.21
0.42
1.20

Start-up Checklist and Log

In order to minimize troubleshooting and costly system
failures, complete the following checks and data entries
before the system is put into full operation.
Heat
Source
Load
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
Operating Data
Water Volume Gallons (U.S)
1.57
3.14
8.98
Cool
Source
Load
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
25

Advertisement

Table of Contents
loading

Table of Contents