Maintenance Schedule - SPX Cooling Technologies Hexacool Air Cooled Condenser none User Manual

Marley mc series fluid cooler
Table of Contents

Advertisement

Maintenance Schedule

Maintenance Service
Inspect General Condition and Operation
Observe Operation of:
Mechanical–motor, pump, fan and drive mechanism
Makeup valve (if equipped)
Inspect for unusual noise or vibration
inspect and Clean:
Air inlet
PVC drift eliminators
Distribution system and nozzles
Collection basin
Fan and pump motor exterior
Coil surface
Check:
Collection water basin level
Blowdown–adjust as required
Lube lines if equipped:
Check for leaks in hoses or fittings
Belt drive:
Fan shaft bearing lubrication (every 3 mo.)
Check and tighten support fasteners
Check shaft, sheave and belt alignment
Check belt tension and condition
Check sheave bushing fastener torque
Fan:
Check fan assembly fasteners
Motor:
Lubricate (grease as required)
Check mounting bolts for tightness
Operate at least
Basin Heater (if equipped):
Check for proper operation of temp/low water level sensor
Inspect/clean buildup of contaminant from sensor
Structure:
Inspect/tighten all fasteners
Inspect and touch up all metal surfaces
R — Refer to Component User Manual
Note: It is recommended at least weekly, that the general operation and condition be observed. Pay
attention to any changes in sound or vibration that may signify a need for closer inspection.
26
Monthly
Semi-annually
x
x
x
x
x
x
x
x
x
x
x
x
every 3 months
3 hours a month
3 hours a month
Seasonal Startup or annually
x
R
every 3 months
x
3 hours a month
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
R
x
x
x
x
x

Advertisement