SPX Cooling Technologies Evaporative Air Cooler FSIG-TS-08A Engineering Data

Marley sigma f series cooling tower

Advertisement

Quick Links

/
/
Marley Sigma F Series
Cooling Tower
Engineering Data & Specifications

Advertisement

Table of Contents
loading

Summary of Contents for SPX Cooling Technologies Evaporative Air Cooler FSIG-TS-08A

  • Page 1 Marley Sigma F Series Cooling Tower Engineering Data & Specifications...
  • Page 2: Table Of Contents

    Marley Sigma F Series Engineering Data Schematic Support Piping Temperature Control Environmental Specifications / Base Base Thermal Performance Construction Fan Deck and Fan Cylinder Mechanical Equipment Fill, Louvers and Drift Eliminators Hot Water Distribution System Casing Access and Safety Cold Water Basin Scope of Work Specifications / Options Cold Water Basin Options...
  • Page 3 Space does not permit definition and explanation of all of the possible options that can be applied to the Sigma F Series. SPX Cooling Technologies realizes that you, the purchaser, must be happy with the tower's characteristics, and we are prepared to provide—or provide for—any reasonable enhancement...
  • Page 4: Schematic

    Marley Sigma F Series COLUMN 3" Use this data for preliminary layouts only. Obtain current drawing from your Marley sales representative. The UPDATE web-based selection software — available at spxcooling.com — provides Sigma F Series model recommendations based on customer's specific design requirements. Tower Model F1211...
  • Page 5: Support

    Marley Sigma F Series COL. & ANCH. BOLT " MAX. NORMAL GAGE SECTION Tower Model Note 4 F1211 F1221 F1231 F1241 F1251 F1261 NOTE 1 Use this bulletin for preliminary layouts only. Do not use for construction. Obtain current drawings from your Marley representative.
  • Page 6 Marley Sigma F Series 6" MIN TOP OF BASIN CURB 1'-6" OPERATING WATER LEVEL RECOMMENDED SECTION B Tower Model Note 4 F1211 F1221 F1231 F1241 F1251 F1261 NOTE 1 Use this bulletin for preliminary layouts only. Do not use for construction. Obtain current drawings from your Marley representative.
  • Page 7: Piping

    Marley Sigma F Series LOADS SUPPORTED TOWER DIAMETER CROSSOVER PIPE MOTOR STAINLESS CONCRETE STEEL BASIN BASIN OPTION OPTION END ELEVATION Tower Flow/Cell Model F1210 1050-5750 F1220 1050-5750 F1230 1320-7200 F1240 1500-8650 F1250 1500-8650 F1260 1850-10100 Cooling Tower Engineering Data : Piping Plan 2 TYP.
  • Page 8 Marley Sigma F Series TYP. SINGLE CELL COLUMN AND ANCHOR BOLT TOWER INLET RISER MOTOR STAINLESS STEEL BASIN END ELEVATION OPTION Tower Flow/Cell Model F1210 1050-5750 12" F1220 1050-5750 14" F1230 1320-7200 14" F1240 1500-8650 14" F1250 1500-8650 16" F1260 1850-10100 16"...
  • Page 9 Marley Sigma F Series TYP. SINGLE CELL COLUMN AND ANCHOR BOLT TOWER INLET RISER MOTOR STAINLESS STEEL BASIN END ELEVATION OPTION NOTE 1 Use this bulletin for preliminary layouts only. Obtain current drawings from your Marley representative. 2 Pumping head contributed by the tower is static lift E. Actual pumping head will vary according to tower circulating GPM.
  • Page 10: Temperature Control

    Marley Sigma F Series Cooling towers are usually selected to produce a specific cold water temperature at the higher summertime wet-bulb temperatures. During the remainder of the year, the cooling tower is capable of producing much colder water. Unless your system will benefit from the coldest possible water tempera- ture, you should consider controlling cold water temperatures to higher levels.
  • Page 11: Environmental

    Marley Sigma F Series Sound Control Sound produced by a Sigma tower operating in an unobstructed environment will meet all but the most restrictive noise limita- tions—and will react favorably to natural attenuation. Where the tower has been sized to operate within an enclosure, the enclosure itself will have a damping effect on sound.
  • Page 12: Specifications: Base

    Marley Sigma F Series Specifications Base: Furnish and install an induced-draft, crossflow-type, field-erected, structural fiberglass-framed, PVC film-fill, industrial- duty cooling tower of _____ cell(s), as shown on Plans. The limiting overall dimensions of the tower shall be _____ wide, _____ long, and _____ high to the top of the fan cylinder.
  • Page 13: Thermal Performance

    Marley Sigma F Series Specifications Thermal Performance: The tower shall be capable of cooling _____ GPM of water from ____ °F to _____ °F at a design entering air wet- bulb temperature of _____ °F . The cool- ing tower manufacturer shall guarantee that the tower supplied will meet the specified performance conditions when the tower is installed according...
  • Page 14: Construction

    Marley Sigma F Series Specifications Construction: The tower shall be capable of with- standing water having a pH of 6.5 to 8.0; a chloride content (NaCl) up to 750 ppm; a sulfate content (SO 4 ) up to 1200 ppm; a calcium content (CaCO 3 ) up to 800 ppm;...
  • Page 15: Fan Deck And Fan Cylinder

    Marley Sigma F Series Specifications Fan Deck and Fan Cylinder: The fan deck shall act as a working platform for maintenance personnel. It shall consist of 1 1/8" (28.5 mm) deep pultruded fiberglass interlocking pan- els, supported by structural fiberglass joists on 3'-0"...
  • Page 16: Fill, Louvers And Drift Eliminators

    Marley Sigma F Series Specifications A stainless steel oil fill and drain line shall extend from the gear reducer to the vicinity of the motor, and shall be equipped with a bronze-bodied oil level sight-glass gauge. The complete mechanical equipment assembly for each cell shall be sup- ported by a rigid, unitized support that resists misalignment between the...
  • Page 17: Hot Water Distribution System

    Marley Sigma F Series Specifications Hot Water Distribution System: The mechanical equipment support/ crossover pipe for each cell shall be equipped with a flange for the attachment of customer supply piping. Inlet and bolt circle dimensions shall conform to 125# flange specifications.
  • Page 18: Access And Safety

    Marley Sigma F Series Specifications Access and Safety: Single cell towers shall include a 33" (838 mm) wide by 61" (1.55 m) high molded FRP access door in one endwall casing for access to the inte- rior of the tower. Casing access door shall be hinged and equipped with a latch operable from both inside and outside the tower.
  • Page 19: Scope Of Work

    Marley Sigma F Series Specifications 11.0 Scope of Work: 11.1 The cooling tower manufacturer shall be responsible for the design, fabrica- tion, and delivery of materials to the project site, and for the erection of the tower over supports provided by others.
  • Page 20: Specifications: Options

    Marley Sigma F Series Specifications Cold Water Basin Options Stainless Steel Cold Water Basin: 10.1 Replace paragraph 10.1 with the following: Include a cold water col- lection basin constructed of 12 gauge series 304 stainless steel, through- bolted and sealed to prevent leakage. A depressed, side outlet sump of series 304 stainless steel having a (6.4 mm) thick faceplate drilled for a...
  • Page 21: Convenience And Safety Options

    Marley Sigma F Series Specifications and a solid state circuit board for tem- perature control and low water cutoff. A control probe shall be located in the basin to monitor water level and tem- perature. The system shall be capable of maintaining 40°F water temperature at an ambient air temperature of ____ °F .
  • Page 22: Plenum Walkway

    Marley Sigma F Series Specifications Plenum Walkway: Add the following to the end of this paragraph: Provide a 30" (762 mm) minimum wide walkway extending from one endwall access door to the other through the length of the tower. Walkway shall be constructed of fiberglass components with a nonskid surface on floor members, and the top of the walkway shall be above the cold...
  • Page 23: Air Inlet Screens

    Marley Sigma F Series Specifications Air Inlet Screens: Add the following paragraph in the Fill, Louvers and Drift Eliminators section: The air inlet faces of the tower shall be covered by 1" mesh stainless steel welded wire screens. Screens shall be secured to stainless steel frames, and shall be removable.
  • Page 24: Control Options

    Marley Sigma F Series Specifications Control Options Control System: Add the following paragraphs in the Mechanical Equipment sec- tion: Each cell of the cooling tower shall be equipped with a UL listed control system in a NEMA 3R or 4X outdoor enclosure capable of control- ling single-speed or two-speed motors as required, and designed specifically...
  • Page 25: Variable Speed Drive

    Marley Sigma F Series Specifications Fan Motor Variable Speed Drive: Marley All Weather ACH550 System Add the following paragraph in the Mechanical Equipment section when VFD is used with customers Building Management System: A complete UL listed Variable Speed Drive system in a NEMA 1 indoor, NEMA 12 indoor or NEMA 3R outdoor enclosure shall be pro- vided.
  • Page 26 Marley Sigma F Series Cooling Tower Specifications: Options Specifications Specification Value and cooling is no longer required. The fluid cooler manufacturer shall supply VFD start-up assistance. Tower vibration testing throughout the speed range is required to identify and lockout any natu- ral frequency vibration levels which may exceed CTI guidelines.
  • Page 27: Vibration Limit Switch

    Marley Sigma F Series Specifications consist of start and stop control, bypass/ VFD selector switch, Auto/Manual selec- tor switch, manual speed control, and solid-state temperature controller. An emergency bypass selector switch inter- nal to the panel allowing the fluid cooler fan motor to be run at full speed shall be furnished.
  • Page 28: Fiberglass Ladder

    Marley Sigma F Series Specifications Fiberglass Ladder: Change paragraph 9.3 to read as follows: One endwall of the tower shall be equipped with an 18" (457 mm) wide fiberglass vertical ladder, supported by hot-dip galvanized steel brackets through-bolted to the endwall structure.
  • Page 29 Marley Sigma F Series Cooling Tower Specifications: Options Specifications Specification Value...
  • Page 30 7401 WEST 129 STREET OVERLAND PARK, KANSAS 66213 UNITED STATES 913 664 7400 spxcooling@ct.spx.com spxcooling.com In the interest of technological progress, all products are subject to design and/or material change without notice. ©2008 SPX Cooling Technologies, Inc. Printed in USA | FSIG-TS-08A...