HANYOUNG NUX GE Series Instruction Manual

HANYOUNG NUX GE Series Instruction Manual

Digital counter & timer

Advertisement

Quick Links

Digital counter & timer
GE series
INSTRUCTION MANUAL
Thank you for purchasing HANYOUNG product.
Please check whether the product is the exactly same as you ordered.
Before using the product, please read this instruction manual carefully.
Please keep this manual where you can view at any time
Safety information
Before using the product, please read the safety information thoroughly and use it properly.
Alerts declared in the manual are classified to Danger, Warning and Caution by their criticality.
DANGER
DANGER indicates an imminently hazardous situation
which, if not avoided, will result in death or serious injury
WARNING
WARNING indicates a potentially hazardous situation
which, if not avoided, could result in death or serious injury
CAUTION indicates a potentially hazardous situation which,
CAUTION
if not avoided, may result in minor or moderate injury
DANGER
Do not touch or contact the input/output terminals because it may cause
electric shock.
WARNING
• If the user use the product with methods other than specified by the
manufacturer, there may be bodily injuries or property damages.
• If there is a possibility of an accident caused by errors or malfunctions of
this product, install external protection circuit to prevent the accident.
• Since this product does not have the power switch or a fuse, please install
those separately on the outside. (Fuse rating: 250V 0.5A)
• To prevent damage or failure of this product, please supply the rated
power voltage.
• To prevent electric shock or equipment failure, please do not turn on the
power until completing wiring.
• Since this is not explosion-proof structure, please do not use in a place
where combustible or explosive gas is around.
• Never disassemble, modify, or repair the product. There is a possibility of a
malfunction, an electric shock, or a risk of fire.
• Please turn off the power when mounting/dismounting of the product. This
is a cause of an electric shock, a malfunction, or failure.
• Since there is a possibility of an electric shock, please use the product as
mounted on a panel while the power is being supplied.
CAUTION
• The contents of the instruction manual are subjective to change without
prior notice.
• Please make sure that the specification is the same as what you have
ordered.
• Please make sure that the product is not damaged during shipping.
• Please use this product in a place where corrosive gas (such as harmful
gas, ammonia, etc.) and flammable gas do not occur.
• Please use this product in a place where there is no direct vibration and a
large physical impact to the product.
• Please use this product in a place where there is no water, oil, chemicals,
steam, dust, salt, iron or others (Contamination class 1 or 2).
• Please do not wipe this product with organic solvents such as alcohol,
benzene and others. (Please use mild detergent)
• Please avoid places where excessive amounts of inductive interference
and electrostatic and magnetic noise occur.
• Please avoid places where heat accumulation occurs due to direct sunlight
or radiant heat.
• Please use this product in a place where the elevation is below 2,000 m.
• Please make sure to inspect the product if exposed to water since there is
a possibility of an electric leakage or a risk of fire.
• If there is a lot of noise from the power line, installing an insulated
transformer or a noise filter is recommended. The noise filter should be
grounded on the panel and the lead wire between the output of the noise
filter and the power terminal of the instrument should be as short as
possible.
• It is effective against noise if making the power lines of the product the
twisted pair wiring.
• Please do not connect anything to the unused terminals.
• Please connect wires properly after making sure the polarity of terminal.
• Please use a switch or breaker (IEC60947-1 or IEC60947-3 approved)
when the product is mounted on a panel.
• Please install a switch or break near the operator to facilitate its operation.
• In order to use this product properly and safely, we recommend periodic
maintenance.
• Some parts of this product have limited expected life span and aged
deterioration.
HANYOUNGNUX CO.,LTD
1381-3, Juan-Dong, Nam-Gu Incheon, Korea.
HEAD OFFICE
TEL:(82-32)876-4697
PT. HANYOUNG ELECTRONIC INDONESIA
JL.CEMPAKA BLOK F 16 NO.02 DELTA SILICON II INDUSTRIAL PARK
INDONESIA
LIPPO CIKARANG CICAU, CIKARANG PUSAT BEKASI 17550 INDONESIA
FACTORY
TEL : 62-21-8911-8120~4 FAX : 62-21-8911-8126
• The warranty of this product (including accessories) is 1 year only when it
is used for the purpose it was intended under normal condition.
• When the power is being supplied there should be a preparation time for
the contact output. Please use a delay relay together when it is used as a
signal on the outside of interlock circuit or others.
Suffix code
Model
Code
GE
-
3
4
Appearance
6
7
P
Type
T
4
Displayable digit
6
1
Setting stage
(excludes the total counter)
2
Power supply voltage
Specification
Model
GE4
Power supply voltage 100 - 240 V a.c 50 - 60 ㎐ , 24 - 60 V d.c/a.c (voltage fiuctuation : ±10 % )
Approx. 13.5 VA(100 - 240 V a.c), approx. 5 W(24 - 60 V d.c),
Power consumption
Charater height( ㎜ )
11 (computed), 8 (set value)
Input counting
speed
(ON/OFF ratio : 1:1, "H" level : 5 - 3 V d.c, "L" level : 0 - 2 V d.c)
Memory back-up
CP1, CP2, RESET, BATCH RESET (exclude TOTAL) 4inputs
Input
[H] level 4 - 30 V d.c, [L] level 0 - 2 V d.c Internal pull up/pull down
resistance connection due to NPN/PNP setup
Counter
External reset Min. input signal range : select among 0.1 ㎳ , 1 ㎳ , 20 ㎳
Min input
signal
Timer
START, INHIBIT, RESET Min. input signal range : select either 1 ㎳ , 20 ㎳
External supplying power
ONE SHOT output
1
level
1c (OUT)
st
2
level
st
capacity
a contact : 250 V a.c 3 A (resistive load), b contact : 250 V a.c 2 A
Control
output
1
level
st
2
level
-
st
capacity
Timer action error
100 ㏁ min (500 V d.c) Between current-carrying terminals and exposed
Insulation
resistance
Dielectric strenght 2000 V a.c 60 Hz for 1 min (diferrerent recharging terminal from each other)
Square wave by the nois simulator (1 ㎲ pulse per 16 ㎳ )
Noise resistance
±2 ㎸ (Power supply terminal), ±500 V (Input terminal)
Vibration resistance
10 - 55 ㎐ , peak amplitude 0.5 ㎜ , 3 axis each direction for 2 hour
Shock resistance
Electrical
100 thousand times min (250 V a.c 2 A resistance load)
Relay life
Mechanical
Protection structure
Storage temperature
Ambient temperature
humidity
Weight
133 g max
※ If you want to input and output type, please contact HANYOUNG sales office
1
MD0106E121109
FAX:(82-32)876-4696
http://www.hynux.net
Description
Digital counter & timer
96(W) × 48(H) ㎜
48(W) × 48(H) ㎜
72(W) × 36(H) ㎜
72(W) × 72(H) ㎜
Preset counter
Total counter (Only for indication)
4 digits (9999) * GE3 and GE7 are not selectable
6 digits (999999)
1 Stage setting
2 Stage setting
A 100 - 240 V a.c 50 - 60 ㎐
D 24 - 60 V d.c / a.c 50 - 60 ㎐
GE6
GE3
Approx. 9 VA(24 - 60 V a.c)
13 (computed), 10 (set value)
1 cps, 30 cps, 1 kcps, 10 kcps
10 years (non-volatile memory)
12 V d.c 100 ㎃ max
0.01 - 99.99 s [OUT1, OUT2(OUT)]
1a (OUT)
1c (OUT)
1a (OUT1), 1c (OUT2)
NPN 2contacts (OUT, BAT.O)
-
NPN 2 contact (OUT1, OUT2)
Open collector, 30 V d.c, 100 ㎃ max
With power start : ±0.01 % ±0.05 sec max
With reset start : ±0.005 % ±0.003 sec max
non-current -carrying metal parts.
300 ㎨ , 3 axis each three times
1 million times min
IP65 (Front part only)
-20 ℃ ~ 65 ℃
-10 ℃ ~ 55 ℃, 35 % ~ 85 % RH
138 g max
203 g max
GE7
203 g max

Advertisement

Table of Contents
loading

Summary of Contents for HANYOUNG NUX GE Series

  • Page 1 MD0106E121109 Digital counter & timer GE series INSTRUCTION MANUAL HANYOUNGNUX CO.,LTD Thank you for purchasing HANYOUNG product. 1381-3, Juan-Dong, Nam-Gu Incheon, Korea. Please check whether the product is the exactly same as you ordered. HEAD OFFICE TEL:(82-32)876-4697 FAX:(82-32)876-4696 http://www.hynux.net Before using the product, please read this instruction manual carefully.
  • Page 2: Power Supply

    Power supply Counter mode setting method During the first 100 ㎳ after power input and first 200 ㎳ after power opening, it is consider as ascend and descend time of internal power and external output power. Therefore, it does not operate during unstable period in order to prevent from malfunction which is caused by unstable output operation of external sensor ※...
  • Page 3 Counter output action mode One shot output of OUT1 output One Shot output time 0.01s~99.99s ※ As for 1 Stage counter (OUT), it is the same as 2ND output (OUT2) action. Self holding output Self holding output Self holding output One shot output of OUT1 output Input Mode Output...
  • Page 4 ※ Input Logic Setup Status can be Timer mode setting method verified in Function Setup Mode. ※ Internal Impedance is 4.7㏀, and switches over to Pull Up or Pull Down from NPN/PNP Selection.(Refer to Input Connection) ※ To prevent chattering during the use of Contact Input Counter, setup the coefficient speed at 1 or 30 cps in Function Setup Mode.
  • Page 5: Output Connection

    Signal START / ON delay Timer time range ▒ Range selection symbol 4 digits time range 6 digits time range DOWN Decimal System Sixagecimal system Decimal System Sixagecimal system 99.99 s 59.99 s 9999.99 s 59 m 59.99 s 999.9 s 9 m 59.9 s 99999.9 s 9 h 59 m 59.9 s...
  • Page 6 Twin timer output action ▒ Interval / Signal START ▒ Power RUN - ON delay • RUNS when POWER is ON • OFF Output for T1 Time / ON for T2 Time. Repetition • Initializes and stops when RESET is ON ▒...
  • Page 7: Batch Counter

    Timer action of exclusive indication(GE-T) Dimension and panel cutout [Unit:㎜] • OFF set is available for the up time range of decimal system (press key for 2 sec) ▒ GE7 ▒ Power RUN Dimension ● 92.0 72.0 72.0 15.0 • In case of when Power is ON, supplying in the RUN RESET signal will initialize the indicating value and setting up the RUN Down mode will start to decrease the value from the set value.
  • Page 8: Connection Diagram

    Connection diagram ▒ GE4-P 2 ▒ GE4-P 1 ※ Connection of NPN input ※ GE4-T6: Total model does not have relay output with transistor. ▒ GE6-P 1 ▒ GE6-P 2 ※ Connection of NPN input ※ GE6-T6 : Total model does not have relay output with transistor. ▒...

This manual is also suitable for: