Terminal DO7 / DO7: Thermostat on Digital output (DC12 V)
• When the thermostat of Dx-coil is ON, a signal comes out.
TCB-IFDMX01UP-E
(Terminal block without relay)
Signal
DC12 V
DO7 -
DOE
GND
DO7 - DOE
Terminal DO8 / DO8: Cooling / heating start up control signal output
• Outputs the start control signal for cooling and heating operation.
Terminal DO9 / DO9: Pre defrost signal
• Output just before defrosting (at least 5 minutes before).
Terminal DOA / DOA: Cool open heat close output
• Heating mode is close, Cooling mode is open.
Terminal DOB / DOB: Notice code output
• Issued when Notice code is output. For details, see the outdoor unit Service Manual.
Terminal DOC / DOC, DOD / DOD, DOE / DOE: FAN speed output
• If select the fan output from interface, use this output. For TA and TF types, the output changes by changing the fan
speed from the remote controller.
DOC = High / DOD = Mid. / DOE = Low
Terminal N1 / N1, N2 / N2: Nothing
The specifications of Terminal DI1 to DI5 are as follows.
• You can switch between voltage and non-voltage with SW701.
SW701
MAX. 1 m
GND
DI1 -
SIGNAL (12 V)
DI1 - DI5
MAX. 2 m
Locally procured
Relay (DC12 V)
OFF
ON
1
Locally procured
DI5
Normally
closed
TCB-IFDMR01UP-E
(Terminal block with relay)
Same as on the left
SW701
SW701
SIGNAL (+)
DI1 -
SIGNAL (-)
DI1 - DI5
– 28 –
OFF
ON
1
MAX. 1 m
Locally procured
Signal Voltage (DC12 V ± 10%)
DI5
GND
28-EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tcb-ifdmr01up-eRbm-a101upva-eRbm-a201upva-e

Table of Contents