Symptom: Dust Comes Out Of The Unit; Symptom: The Units Can Give Off Odours; Symptom: The Outdoor Unit Fan Does Not Spin; Symptom: The Display Shows "88 - Daikin VRV IV+ RXYTQ8U5/U7YF Installation And Operation Manual

Heat pump for high ambient temperatures
Table of Contents

Advertisement

9 Relocation

8.2.12

Symptom: Dust comes out of the unit

When the unit is used for the first time in a long time. This is
because dust has gotten into the unit.
8.2.13

Symptom: The units can give off odours

The unit can absorb the smell of rooms, furniture, cigarettes, etc.,
and then emit it again.
8.2.14
Symptom: The outdoor unit fan does not
spin
During operation. The speed of the fan is controlled in order to
optimise product operation.
8.2.15

Symptom: The display shows "88"

This is the case immediately after the main power supply switch is
turned on and means that the user interface is in normal condition.
This continues for 1 minute.
8.2.16
Symptom: The compressor in the outdoor
unit does not stop after a short heating
operation
This is to prevent refrigerant from remaining in the compressor. The
unit will stop after 5 to 10 minutes.

For the installer

11

About the box

11.1

About

is part of Daikin's wider commitment to reduce our
environmental footprint. With
economy for refrigerants. One of the actions to achieve this, is the
reuse of reclaimed refrigerant in VRV units produced and sold in
Europe. For more information about the countries that are in scope,
visit: http://www.daikin.eu/loop-by-daikin.
11.2
To remove the accessories from
the outdoor unit
Make sure that all accessories are available in the unit.
a
b
c
REQUEST FOR THE INDICATION OF INSTALLATION INFORMATION
BE SURE TO FILL OUT THE BLANKS, WHICH ARE NEEDED FOR AFTER-SALE SERVICES.
1. RECORD OF INDOOR UNIT MODEL AND INSTALLATION SITE
No.
1
2
3
4
5
6
7
8
MODELNAME
INSTALLATION
No.
SITE
11
12
13
14
15
16
17
18
MODELNAME
INSTALLATION
No.
SITE
21
22
23
24
25
26
27
28
MODELNAME
INSTALLATION
SITE
No.
31
32
33
34
35
36
37
38
MODELNAME
INSTALLATION
SITE
No.
41
42
43
44
45
46
47
48
MODELNAME
INSTALLATION
SITE
No.
51
52
53
54
55
56
57
58
MODELNAME
INSTALLATION
SITE
No.
61
62
63
64
MODELNAME
INSTALLATION
SITE
2. RECORD FOR SETTINGS (CONTENTS SEE INSTALLATION MANUAL)
SETTING
VALUE
REMARK
DATE
SETTING
VALUE
REMARK
3. RECORD OF INSTALLATION DATE
DAY
MONTH
YEAR
4. MODEL NAME
5. MANUFACTURING NUMBER
6. AFTER EQUIPPING, PLEASE PUT IT ON THE BACK SIDE OF THE FRONT PLATE.
a
General safety precautions
b
Installation manual and operation manual
c
Additional refrigerant charge label
d
Installation information sticker
e
Piping accessory bag
Installation and operation manual
12
we want to create a circular
d
e
REQUEST FOR THE INDICATION OF ADDITIONAL REFRIGERANT CHARGING AND LEAK DETECTION OPERATION RESULT
BE SURE TO FILL OUT THE BLANKS, WHICH ARE NEEDED FOR AFTER-SALE SERVICES.
9
10
1. CALCULATION OF ADDITIONAL REFRIGERANT CHARGING AMOUNT
CALCULATE THE ADDITIONAL REFRIGERANT CHARGING AMOUNT BASED ON THE FORMULA BELOW BEFORE CHARGING.
SHIPMENT (INDICATED ON THE MACHINE NAMEPLATE) AND THE ADDITIONAL AMOUNT SHOWN AS FOLLOWS :
WHEN RE-CHARGING TOTAL AMOUNT OF REFRIGERANT , CHARGE THE TOTAL OF THE AMOUNT CHARGED AT
19
20
Total indoor unit
capacity connection
Total indoor unit capacity
kg
ratio (CR)
50%< CR < 105%
8HP
0
10-12HP 14-16HP 18-20HP
0
0
0.5
OUTDOOR
AMOUNT
ADDITIONAL CHARGING
TOTAL LENGTH OF LIQUID
PIPE SIZE O22.2 x 0.37
PIPE SIZE O19.1 x 0.26
TOTAL LENGTH OF LIQUID
PIPE SIZE O15.9 x 0.18
TOTAL LENGTH OF LIQUID
when piping length <30m
105%< CR < 130%
50%< CR < 70%
0.5
0
0.5
0
0.5
0
0.5
1.0
29
30
UNIT
kg
(m) x 0.37
(m) x 0.26
(m) x 0.18
Total indoor unit capacity
70%< CR < 85%
0.3
0.5
0.5
1.0
when piping length >30m
85%< CR < 105%
105%< CR < 130%
1.2
0.7
1
1.5
1.5
1
1.5
2.0
PIPE SIZE O12.7 x 0.12
TOTAL LENGTH OF LIQUID
PIPE SIZE O9.5 x 0.059
TOTAL LENGTH OF LIQUID
PIPE SIZE O6.4 x 0.022
TOTAL LENGTH OF LIQUID
39
40
(m) x 0.12
(m) x 0.059
(m) x 0.022
RYYQ8~12
ONLY FOR RYYQ8~20 MODELS
RYYQ14-16
RYYQ18-20
kg
0.9
1.1
1.3
2. RECORD OF ADDITIONAL REFRIGERANT CHARGE AMOUNT AND RESULT OF LEAK CHECK OPERATION
49
50
DATE
AMOUNT
59
60
RESULT LEAK CHECK
DATE
AMOUNT
RESULT LEAK CHECK
DATE
AMOUNT
DATE
RESULT LEAK CHECK
DATE
AMOUNT
RESULT LEAK CHECK
3. FOR DETAILS CONCERNING PIPING SELECTION AND CALCULATION OR HOW TO OPERATE THE LEAK DETECTION FUNCTION, PLEASE REFER TO THE INSTALLATION MANUAL.
4. AFTER FILLING IN THIS TABLE, PLEASE PUT IT ON THE SWITCH BOX COVER.
3P328191-1
3P328192-1
8.2.17
Symptom: The inside of an outdoor unit is
warm even when the unit has stopped
This is because the crankcase heater is warming the compressor so
that the compressor can start smoothly.
8.2.18
Symptom: Hot air can be felt when the
indoor unit is stopped
Several different indoor units are being run on the same system.
When another unit is running, some refrigerant will still flow through
the unit.
9
Relocation
Contact your dealer for removing and reinstalling the total unit.
Moving units requires technical expertise.
10

Disposal

This unit uses hydrofluorocarbon. Contact your dealer when
discarding this unit.
NOTICE
Do NOT try to dismantle the system yourself: dismantling
of the system, treatment of the refrigerant, oil and other
parts MUST comply with applicable legislation. Units
MUST be treated at a specialised treatment facility for
reuse, recycling and recovery.
11.3

Accessory pipes: Diameters

Accessory pipes (mm)
Gas pipe
▪ Front connection
ID Øa
ID Øb
▪ Bottom connection
ID Øa
OD Øb
Liquid pipe
▪ Front connection
ID Øb
ID Øa
▪ Bottom connection
ID Øb
ID Øa
11.4

To remove the transportation stay

Only for 14+16 HP
VRV IV+ heat pump for high ambient temperatures
HP
Øa
Øb
8
25.4
19.1
10
22.2
12
28.6
14
16
8
9.5
10
12
9.5
12.7
14
12.7
16
RXYTQ
4P546223-1C – 2021.11