Multi V S
Outdoor Unit
8. Electrical Wiring
8.3 Automatic Addressing
The address of indoor units would be set by auto addressing
1. Wait for 3 minutes after supplying power.
2. Press RED button of the outdoor units for 5 seconds. (SW01C)
3. A "88" is indicated on 7-segment LED of the outdoor unit PCB.
4. For completing addressing, 2~7 minutes are required depending on numbers of connected indoor units
5. Numbers of connected indoor units whose addressing is completed are indicated for 30 seconds on
7-segment LED of the outdoor unit PCB
6. After completing addressing, address of each indoor unit is indicated on the wired remote control display
window. (CH01, CH02, CH03, ......, CH06 : Indicated as numbers of connected indoor units)
 Main PCB (Standard model)
 Display PCB (Compact model)
CAUTION
In replacement of the indoor unit PCB, always perform Auto addressing setting again (At that time,
please check about using Independent power module to any indoor unit.)
If power supply is not applied to the indoor unit, operation error occur.
Auto addressing is only possible on the Unit.
Auto addressing has to be performed after 3 minutes to improve communication.
DIP-SWITCH
7 - Segment
DIP SWITCH
SW04C (
: cancel)
SW03C (
: forward)
SW02C (
: backward)
SW01C ( ● : confirm)
SW01D (reset)
SW01C ( : confirm)
7-Segment
SW02C ( : backward)
SW03C ( : forward)
SW01D (reset)
SW04C ( X : cancel)
Installation of Outdoor Units
27