Alternative Refrigerant R410A - LG ARUN040GSS0 Manual

Hide thumbs Also See for ARUN040GSS0:
Table of Contents

Advertisement

Multi V S
Outdoor Unit

1. Alternative Refrigerant R410A

The refrigerant R410A has the property of higher operating pressure in comparison with R22.
Therefore, all materials have the characteristics of higher resisting pressure than R22 ones and this
characteristic should be also considered during the installation.
R410A is an azeotrope of R32 and R125 mixed at 50:50, so the ozone depletion potential (ODP) of R410A is 0.
CAUTION
The wall thickness of the piping should comply with the relevant local and national regulations for the designed
pressure 3.8MPa
Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state.
If the refrigerant is charged in its gaseous state, its composition changes and the system will not work properly.
Do not place the refrigerant container under the direct rays of the sun to prevent it from exploding.
For high-pressure refrigerant, any unapproved pipe must not be used.
Do not heat pipes more than necessary to prevent them from softening.
Be careful not to install wrongly to minimize economic loss because it is expensive in comparison with R22.
2
Installation of Outdoor Units

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents