Download Print this page

Honeywell R7426A Manual page 13

Temperature and universal input controllers
Hide thumbs Also See for R7426A:

Advertisement

Default Programming DefProg (C.23)
R7426D controllers also have the DefProg (C.23) parameter.
Setting DefProg to 1 resets parameter values to default (see
Tables 9 and 10 for default values). After default
programming, DefProg is reset to 0.
NOTE: A display of def indicates default programming.
Span Adjustment: UStartPoint/UendPoint (C.24/C.25)
I01 and I02 accept any analog inputs within the range of 0 to
10 Vdc. They also provide an input span adjustment to match
the connected transmitter range.
Input span start and end points can be adjusted with
UStartPoint and UendPoint. After adjustment, the span
converts to a 0 to 100 percent input range.
NOTE: UStartPoint and UEndPoint are common for both
inputs I01 and I02.
OffDelay for On/Off Output (C.26)
On/Off output is controlled by the Plant/System On/Off input. It
provides an Off switching output with adjustable delay time.
This can operate, for example, a fan for a certain time after
humidification ends.
Table 11. OffDelay.
Input
Function
On
Normal control
Off
Output O1 is 0
percent
StartTime (C.28)
The StartTime determines the time in the start-up routine
during which the W1 setpoint decreases from its temporary
value to the normal programmed value.
NOTE: This only operates with an OAT sensor connected
and the OAT is below 42°F.
Parameter Settings and Adjustment
High/Low Limit Setpoint: W
For high or low limit control, parameter W
During limit control, the throttling range Xp2 and reset time tr2
are active. Limit control is active only when I02 temperature
signal (I02ext is 0) is available, or sensor I01 (I02ext is 1) is
used for limit control.
For cascade control, limit setpoint W
control point at which:
• Submaster setpoint (W
cas
• W
is not shifted by the master control loop.
lim
NOTE: High or low limit control is in accordance with the
configuration parameter LimTyp (C.13).
R7426A,B,C,D TEMPERATURE AND UNIVERSAL INPUT CONTROLLERS
Switching Action Delay in min.
Off to On
0
On to Off
0 to 60
(P.02)
lim
is the setpoint.
lim
determines the
lim
) maintains the limit value.
Compensation Changeover Point: W
The parameter W
comp
winter compensation. Compensation is performed:
• Above W
for summer compensation.
comp
• Below W
for winter compensation.
comp
Summer/Winter Reset: Su/Wi (P.04/P.05)
Summer/Winter reset settings determine the compensation
sensor (I03) reset effect (I0Comp) on the main setpoint (W1).
To calculate winter and summer reset, throttling range must be
considered in proportional-only control (see Tables 12 and 13.)
NOTE: Compensation changeover (Xp) at +20°C OAT with
either P+I or P+I+D control is 0.
Table 12. R7426A,B,C Summer/Winter Reset Calculation.
Control
Room
Schedule
Temperature (I01)
Winter
68°F (20°C)
72°F (22°C)
AutWi
=
Summer
68°F (20°C)
79°F (26°C)
AutSu
=
Table 13. R7426D Summer/Winter Reset Calculation.
Control
Humidity
Schedule
Winter
50% rh
(negative
40% rh
reset)
AutWi
Summer
50% rh
(positive reset)
60% rh
AutSu
Reset Span Adjustment: R
The reset span adjustment (R
in either degrees (R7426A,B,C) or percent (R7426D). If I01
(I01) deviates by 50 percent of the throttling range (Xp1), this
effect alters the submaster setpoint (W
Throttling Range: Xp1/Xp2 (P.08/P09)
Throttling range (Xp) adjustment determines the change
required at the main sensor and limit or cascade sensor to
operate the output device through full stroke. Xp1 is the main
control loop throttling range. Xp2 is used when limitation or
cascade control (submaster control loop) are active (see
Table 14).
13
comp
defines the start point of summer or
OAT
(I03/I0comp)
68°F (20°C)
5°F (-15°C)
(
)
∆I01
22 20
+
2
+
Xp
------------------------ -
------------------------------- -
=
∆OAT
35
68°F (20°C)
95°F (35°C)
∆I01 Xp
(
) 2
26 20
------------------------ -
-------------------------------
=
∆OAT
15
OAT
(I01)
(I03/I0comp)
Range (Xp)
68°F (20°C)
5% rh
5°F (-15°C)
(
∆X1
40 50
+
Xp
----------------------- -
------------------------------- -
=
=
∆OAT
35
68°F (20°C)
5% rh
95°F (35°C)
∆X1
(
+
Xp
60 50
----------------------- -
-------------------------------
=
=
∆OAT
15
(P.07)
cas
) determines the reset effect
cas
).
cas
(P.03)
Throttling
Range (XP)
3.6°F (2°C)
0.12
3.6°F (2°C)
0.27
Throttling
)
+
5
0.14
) 5
0.33
63-2565