Westinghouse WHU09DHA21S Service Manual page 48

Duct type
Table of Contents

Advertisement

ESP setting
The static pressure can be freely adjusted by using specific wired remote controller.
LCD
Fig 6.2
Static pressure setting:
Press and hold "MODE" button and "ADD.FUNC." button for 3 seconds, symbol
1
starts blinking at the same time.
Press" / "button to adjust parameter number until "17" is displayed, and press "ENTER"button to enter
2
system parameter adaption state, symbol
Select desired parameter code 10 by pressing " / " button, and press "ENTER" button to confirm.
3
Select desired function code to rewrite the parameter values by pressing " /
4
"ENTER" button to confirm.
Press "ON/OFF" button or "CANCEL"button to quit.
5
Model
Error Indicator
(Capacity
Parameter
Btu/h)
Code
9K/12K/18K
Function Code
24K
36K
stops blinking.
- 47 -
The Range
of
Function Code Set
Static
Pressure
0-50 function code value equals
0-0.20 in. H O
static pressure value,
2
(0-50Pa)
more than 50 is 0.20 in. H O (50Pa),
[default: 0 (0.18 in. H O or 45Pa)]
0-100 function code value equals
0-0.40 in. H O
static pressure value,
2
(0-100Pa)
more than 100 is 0.40 in. H O (100Pa),
[default: 0 (0.18 in. H O or 45Pa)]
0-140 function code value equals
0-0.56 in. H O
static pressure value,
2
(0-140Pa)
more than 140 is 0.56 in. H O (140Pa),
[default: 0 (0.23 in. H O or 57Pa)]
and parameter code
"button, and press
2
2
2
2
2
2