Electrical Characteristics - Westinghouse WHM24DMA21S Design & Technical Manual

Duct type
Hide thumbs Also See for WHM24DMA21S:
Table of Contents

Advertisement

6. Electrical characteristics

If you use the optional heater kit, make sure if it is suitable for the 3-way installation of the AHU.
Air
Heater kit
Electric
handler
model
heat
model
name
(kW)
2105340
24K
2105342
7.5
2105343
10
2105340
2105342
7.5
36K
2105343
10
2105344
15
2105340
2105342
7.5
48K, 60K
2105343
10
2105344
15
2105345
20
• ●: available
• —: unavailable
NOTES:
• As the wire size and circuit breaker regulations differ in each country or region, select appropri-
ate devices comply with the regional standard.
• Fan speed selection:
– 2: Medium-low
– 3: Medium
– 4: Medium-high
– 5: High
• Connect the heater kit to the power supply separately.
• Ampacities for MCA*
• Heat pump systems require specified airflow. Each ton of cooling requires between 350 and 450
CFM/Ton, or 400 CFM/Ton usually.
*1: Minimum Circuit Ampacity (Calculation based on UL60335-2-40)
*2: Maximum Circuit Breaker
1
MCA*
(A)
AC 230 V
AC 208 V
5
28.3
40.7
53.2
5
29.8
42.2
54.7
42.2 + 36.9
38.6 + 33.8
5
31.8
44.8
56.7
44.8 + 36.9
40.7 + 33.8
56.7 + 49.9
51.9 + 45.2
1
and MAX. CKT. BKR*
MAX. CKT. BKR*
AC 230 V
AC 208 V
25.9
30
37.2
45
48.5
60
27.4
30
38.7
45
49.9
60
45 + 40
40 + 35
29.4
35
40.7
45
51.9
60
50 + 40
50 + 35
60 + 50
60 + 50
2
include the blower motor.
- 17 -
2
Fan speed tap
(A)
2
3
4
30
40
50
30
40
50
30
45
55
6. Electrical characteristics
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents