Trouble Indications - Faraday MPC-NET2 Owner's Manual

Mpc-net system networking
Table of Contents

Advertisement

Trouble Indications

All panels and network annunciators connected to the network will indicate network specific faults (see Section III for
details). Individual panel system troubles (ground fault, battery, etc) will not be transmitted to other fire panels but will
be transmitted to the RND-2s, network printers and simple monitoring computers.
All initiating devices on the MPC-6000 or MPC-7000 can also be programmed to a network LINK (accomplished while
configuring devices on the panel). The maximum LINK number for the MPC-6000 and MPC-7000 is 255. If an
initiating device on a panel goes into trouble, and it has been programmed to a network LINK, it will send a network
message to the other panels indicating that the network LINK is in trouble. If other panels on the network have that
LINK number programmed, they will also indicate the trouble as configured.
Other panels will display:
TRB
xxx/yyy 10:12
40 character custom
link message
NN:L175 NETWORK LINK
RND-2s will display:
TRB
xxx/yyy 10:12
40 character custom
link message
NN:xxxx Device type
When the trouble event has been restored, the display will show below;
Other panels will display:
R/TRB xxx/yyy 10:12
40 character custom
link message
NN:L175 NETWORK LINK
RND-2s will display:
R/TRB xxx/yyy 10:12
40 character custom
link message
NN:xxxx Device type
P/N 315-049594-1
Explanation of display/history event:
This is x of y troubles in the system that was logged at 10:12 (24 hour time)
These two lines will indicate a custom message for the network link
Bottom line indicates that node link 175 on node nn is the source of the
trouble. The plus sign at the end indicates that there are more
Explanation of display/history event:
The RND-2 if configured for this will also show the individual point information.
Explanation of display/history event:
This is a restoral of x of y troubles in the system that was logged at 10:12 (24
hour time)
These two lines will indicate a custom message for the network link
Bottom line indicates that node link 175 on node nn is the source of the
trouble. The plus sign at the end indicates that there are more
Explanation of display/history event:
The RND-2 if configured for this will also show the individual point information
for the trouble restoral.