12603A NETWORK INTERFACE BOARD
The 12603 or 12603A Network Interface Board is a module to interface between the MPC-6000 or MPC-7000 Fire
Alarm System Control Unit and the FARADAY MPC-NET2 Network. The NIB mounts inside the MPC-6000 cabinet.
P/N 315-049594-1
19
firealarmresources.com
Notes:
1.) Units to be installed in
accordance with all local
codes.
2.) T-Tapping is not allowed!
Communication wiring must
be daisy chained from
network interface board to
network interface board.
3.) Use Category 5 wire with a
3000 feet maximum
distance from network
interface module to network
interface module.
4.) 12525 is required when
network wiring leaves the
building.