Oil Piping − One-Pipe System
Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó
Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó
Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó
Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó
Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó
Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó
Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó
Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó
Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó
Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó
To determine the correct tubing size for piping, refer to
table 3 .
One−Pipe Oil Line Sizing
Line Length
0−50' (15 m)
51−100' (15 m)
Two−Pipe System
When using a two−pipe system (see figure 16) with the oil
tank below the level of the burner, use a single−stage fuel
pump in lift conditions of up to 10 feet (3 m) and/or a vacu-
um of 10" (254 mm) Hg or less. Use a two−stage fuel pump
when lift exceeds 10 feet (3 m) and/or a vacuum of 10" (254
mm) Hg to 15" (381 mm) Hg. Both conditions require that
you use of a two−pipe system, which consists of a return
line that purges the fuel pump of air by returning it to the
tank. To determine the run and lift for piping, refer to table 4
.
Use continuous lengths of heavy wall copper tubing or
steel pipe for oil supply pipe. Install oil supply pipe under
floor or near walls to protect it from damage. Avoid running
pipes along joists or reverberating surfaces. Always use
flare fittings. All fittings must be accessible. Do not use
compression fittings.
Downloaded from
ManualsNet.com
AIR VENT
FILL PIPE
FUEL PUMP
OIL
TANK
SHUT−OFF
VALVE
Figure 15
Table 3
Pipe Diameter (OD Tubing)
3/8" (10 mm)
1/2" (12 mm)
search engine
AIR VENT
FILL PIPE
AUX
Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó
FILTER
Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó
Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó
8 ft (2.4 m)
Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó
Maximum
One Pipe Lift
Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó
RETURN
PIPE
outside tank fuel pump above bottom of tank.
Both oil supply and return pipes must be sub-
merged in oil in the supply tank.
Two−Pipe Maximum Pipe Length (H + R)
Lift H"
ft (m)
0' (0.0)
2' (0.6)
4' (1.2)
6 ' (1.8)
8' (2.4)
10' (3.0)
12' (3.7)
14' (4.3)
16' (4.9)
18' (5.5)
Page 11
Oil Piping − Two-Pipe System
RETURN
PIPE
OIL
TANK
3"−4"
(76 mm −102 mm)
R
Figure 16
IMPORTANT
Table 4
3450 RPM − 3 GPH (11.4 LPH)
Single−
Two−
Stage
Stage
3/8" (10 mm) OD
Tubing − ft (m)
84 (25.6)
93 (28.3)
73 (22.3)
85 (25.9)
63 (19.2)
77 (23.5)
52 (15.8)
69 (21.0)
42 (12.8)
60 (18.3)
31 (9.4)
52 (15.9)
21 (6.4)
44 (13.4)
−−−
36 (11.0)
−−−
27 (8.2)
−−−
−−−
FUEL PUMP
AUX
FILTER
INLET
H
Single−
Two−
Stage
Stage
1/2" (12 mm) OD
Tubing
100 (30.5)
100 (30.5)
100 (30.5)
100 (30.5)
100 (30.5)
100 (30.5)
100 (30.5)
100 (30.5)
100 (30.5)
100 (30.5)
100 (30.5)
100 (30.5)
83 (25.3)
100 (30.5)
41 (12.5)
100 (30.5)
−−−
100 (30.5)
−−−
76 (23.2)