2. ENCODING AND CONSTRUCTION ..................................3 3. MECHANICAL INSTALLATION ....................................4 4. ELECTRICAL INSTALLATION ....................................5 5. FLOW RATE REGULATION .......................................7 6. PERIODICAL MAINTENANCE ....................................10 7. TECHNICAL DATA ........................................10 UAB KOMFOVENT we reserve the right to make changes without prior notice PPU-LCHX_21-05...
2. ENCODING AND CONSTRUCTION PPU-LCHX is a pipework package unit for liquid coupled heat exchangers that are used for heat/cold recovery in the air handling units (AHU). PPU ensures proper circulation of thermal medium (usually mixture of glycol and water) throughout the piping circuit, regulates requperation efficiency and prevents coils from freezing.
3. MECHANICAL INSTALLATION PPU-LCHX to be installed in technical room, where ambient temperature is 0..+40°C. Unit must be mounted on a flat and sturdy base or on a construction specially designed for mounting. If mounting base ins not flat, PPU can be leveled using adjustable feet at the bottom of the frame.
1 – Frequency inverter control terminals, 2 – Pump connection terminals, 3 – Main power terminals 4 – Micro switch configuration, 5 – Control panel connection (RJ9) UAB KOMFOVENT we reserve the right to make changes without prior notice PPU-LCHX_21-05...
Page 6
• For information on how to connect frequency converter to the AHU automation control, please follow electrical wiring diagram of the AHU. UAB KOMFOVENT we reserve the right to make changes without prior notice PPU-LCHX_21-05...
0 - Stop 1 - Run 0.0 Hz 0.0 Hz Page 1 Page 1 1 - Run 2 - Fire mode 0 - Stop 0 - Stop UAB KOMFOVENT we reserve the right to make changes without prior notice PPU-LCHX_21-05...
Page 8
Output freq. 4.0 Hz 0.0 Hz [102] Maximum output freq., Hz 80.0 Hz [103] Skip frequency 1, Page 1 0.0 Hz Configuration Op. settings 0 - Stop UAB KOMFOVENT we reserve the right to make changes without prior notice PPU-LCHX_21-05...
Page 9
11. Turn ON main power of the inverter and start AHU. Check operation of the liquid coupled heat exchanger and PPU-LCHX. UAB KOMFOVENT we reserve the right to make changes without prior notice PPU-LCHX_21-05...
If there is a need to perform any mechanical works on the piping circuit (for example to tighten couplings or to clean water filter and etc.) disconnect PPU and AHU from the mains power. It is recommended to carry out PPU-LCHX periodical maintenance at least once a year. If needed register performed works in the maintenance log.
Page 11
DN20-DN32 42-92 DN40-DN65 42-92 UAB KOMFOVENT we reserve the right to make changes without prior notice PPU-LCHX_21-05...
Page 12
LITHUANIA PARTNERS UAB KOMFOVENT J. PICHLER Gesellschaft m. b. H. www.pichlerluft.at TECHNINĖS PRIEŽIŪROS SKYRIUS / Ventilair group www.ventilairgroup.com SERVICE AND SUPPORT ACB Airconditioning www.acbairco.be Phone: +370 5 200 8000 Email: service@komfovent.com REKUVENT s.r.o. www.rekuvent.cz www.komfovent.com WESCO AG www.wesco.ch SUDCLIMATAIR SA www.sudclimatair.ch...