Charging Specifications; Unit Specifications - Teledyne TDMC+ Manual

12 and 24 vdc, lead-acid battery charger
Table of Contents

Advertisement

TDMC+ Teledyne Dual Mode Charger

Charging Specifications

General Parameters
Maximum Charging Current
Standby battery Drain
Voltage Regulation
Output noise and ripple
Efficiency
3 Stage Parameters
Max Absorption Voltage
Absorption to Float Current
Float Voltage
Overvoltage Protection
2 Stage Parameters
Duration of Stage 1 + 2
Max Absorption Voltage

Unit Specifications

Electrical Input
Electrical Output
Environment
Certification
Mechanical Dimensions
(unit only)
Questions?
Write to:
support@teledynebattery.com
Or call: 1 (800) 456 0070 / 1 (909) 793 3131.
12V Specification
<100 uA with AC disconnected
Minimum 85% under worst line/load conditions
12V Specification
14.4V +/- 100mV
500mA +/1 100mA
13.15V +/- 100mV
15.2V +/- 200mV
12V Specification
15.0V +/- 100mV
Voltage
85 VAC – 270 VAC, 50/60 Hz
Max Power
250 Watts
Configuration
Line, neutral, chassis ground
Connector
IEC 60320 C14 power inlet (C13 cord plug)
Supplied Cable
18AWG grounded cord with NEMA 5-15
grounded Type B wall connector
Voltage
32 VDC maximum
Current
6A maximum
Configuration
Positive, Negative
Connector
Two pin circular
Supplied Cable
14 AWG battery cord with crocodile style
battery clips
Orientation
May be used horizontally or vertically
Location
For indoor use only.
Operation
-22F to 140F (-30C to 60C)
Storage
-40F to 176F (-40C to 90C)
UL (U.S)
Under Evaluation
CUL (Canada)
Under Evaluation
CE
Under Evaluation
FCC
Compliant to Part 15 of FCC Rules
Height
11.5" (290mm)
Depth
5" (130mm)
Width
6" (150mm)
Weight
6 lbs (2.7 Kg)
24V Specification
6A +/- .5A
+/- .5%
<150mV, 100MHz BW
24V Specification
28.8V +/- 100mV
500mA +/1 100mA
26.30V +/- 100mV
30.4 +/- 200mV
24V Specification
10 – 80 hours, selectable
30.0V +/- 100mV
Page 13/15