ABOUT THIS MANUAL Purpose This manual describes the assembly, installation, operation and troubleshooting of this unit. Please read this manual carefully before installations and operations. Keep this manual for future reference. Scope This manual provides safety and installation guidelines as well as information on tools and wiring. SAFETY INSTRUCTIONS WARNING: This chapter contains important safety and operating instructions.
INTRODUCTION This hybrid PV inverter can provide power to connected loads by utilizing PV power (DC), utility power (AC) and battery power (DC). Figure 1 PV System Overview Depending on different power situations, this hybrid inverter is designed to generate continuous power from PV solar modules (solar panels), battery, and the utility.
Product Overview NOTE: For parallel installation and operation, please check Appendix I. RGB LED ring (refer to LCD Setting section for the details) LCD display Function buttons PV connectors AC input connectors AC output connectors (Load connection) Battery connectors Current sharing port Parallel communication port 10.
INSTALLATION Unpacking and Inspection Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items inside of package: Inverter User manual Communication cable Preparation Before connecting all wirings, please take off bottom cover by removing two screws as shown below. Mounting the Unit Consider the following points before selecting where to install: Do not mount the inverter on flammable construction...
Install the unit by screwing three screws. It’s recommended to use M4 or M5 screws. Battery Connection CAUTION: For safety operation and regulation compliance, it’s requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it’s still requested to have over-current protection installed.
WARNING: Shock Hazard Installation must be performed with care due to high battery voltage in series. CAUTION!! Do not place anything between the flat part of the inverter terminal and the ring terminal. Otherwise, overheating may occur. CAUTION!! Do not apply antioxidant substance on the terminals before terminals are connected tightly.
→Ground (yellow-green) L→LINE (brown or black) N→Neutral (blue) 5. Make sure the wires are securely connected. CAUTION: Important Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause utility short-circuited when these inverters are worked in parallel operation. CAUTION: Appliances such as air conditioner are required at least 2~3 minutes to restart because it’s required to have enough time to balance refrigerant gas inside of circuits.
Please follow below steps to implement PV module connection: 1. Remove insulation sleeve 10 mm for positive and negative conductors. 2. Check correct polarity of connection cable from PV modules and PV input connectors. Then, connect positive pole (+) of connection cable to positive pole (+) of PV input connector.
Communication Connection Serial Connection Please use supplied communication cable to connect to inverter and PC. Insert bundled CD into a computer and follow on-screen instruction to install the monitoring software. For the detailed software operation, please check user manual of software inside of CD. Wi-Fi Connection Wi-Fi module can enable wireless communication between off-grid inverters and monitoring platform.
OPERATION Power ON/OFF Once the unit has been properly installed and the batteries are connected well, simply press On/Off switch to turn on the unit. Operation and Display Panel The operation and display panel, shown in below chart, is on the front panel of the inverter. It includes one RGB LED ring, four touchable function keys and a LCD display, indicating the operating status and input/output power information.
LCD Display Icons Icon Function description Input Source Information Indicates the AC input voltage and frequency. Indicates the PV voltage, current and power. Indicates the battery voltage, charging stage, configured battery parameters, charging or discharging current. Configuration Program and Fault Information Indicates the setting programs.
Page 14
Indicate the output voltage, load in VA, load in Watt and output frequency. Battery Information Indicates battery level in battery mode and charging status in line mode by 0-24%, 25-49%, 50-74% and 75-100%. When battery is charging, it will present battery charging status. Status Battery voltage LCD Display...
Page 15
Output source priority setting display Indicates setting program 01 “Output source priority” is selected as “SUB”. Indicates setting program 01 “Output source priority” is selected as “SBU”. AC Input Voltage Range Setting Display Indicates setting program 02 is selected as “ ”.
LCD Setting After pressing and holding ENTER button for 3 seconds, the unit will enter setting mode. Press “UP” or “DOWN” button to select setting programs. And then, press “ENTER” button to confirm the selection or ESC button to exit. Program Description Selectable option...
Page 17
240Vac 50Hz (default) 60Hz Output frequency Charge battery first (default) Solar energy provides power to charge battery as first priority. Solar supply priority Power the loads first Solar energy provides power to the loads as first priority. Bypass disable Bypass enable (default) Overload bypass: When enabled, the unit will...
Page 18
If this inverter/charger is working in Line, Standby or Fault mode, charger source can be programmed as below: Solar first Solar energy will charge battery as first priority. Utility will charge battery only when solar energy is not available. Solar and Utility (default) Solar energy and utility will charge Charger source priority: To configure charger...
Page 19
100A 110A (only for 5.6KW/6KW model) 120A (only for 5.6KW/6KW model) AGM (default) Flooded User-Defined If “User-Defined” is selected, battery charge voltage and low DC cut-off voltage can be set up in program 17, 18 and 19. Pylontech battery If selected, programs of 11, 17, 18 and 19 will be automatically set up.
Page 20
party Lithium battery If selected, programs of 02, 26, 27 and 29 will be automatically set up. No need for further setting. Please contact the battery supplier for installation procedure. Default setting: 56.4V If self-defined is selected in program 14, this program can be set up. Bulk charging voltage Setting range is from 48.0V to 64.0V.
Page 21
Return to default display If selected, no matter how users screen (default) switch display screen, it will automatically return to default display screen (Input voltage /output voltage) after no button is pressed for Auto return to default 1 minute. display screen Stay at latest screen If selected, the display screen will stay at latest screen user finally...
Page 22
L3 phase The inverter is operated in L3 phase in 3-phase application. Reset Not reset(Default) Reset PV energy storage 00:00 (Default) The setting range of start charging time for AC charger is from 00:00 to Start charging time for 23:00, increment of each click is 1 AC charger hour.
Page 23
On/Off control for RGB Enabled (default) Disable *It’s necessary to enable this setting to activate RGB LED lighting function. Normal (default) Brightness of RGB LED High Normal (default) Lighting speed of RGB High Power cycling Power wheel RGB LED effect Power chasing Solid on (Default) LED lighting portion will be changed...
Page 24
LED lighting portion will be changed by battery capacity percentage. Battery capacity percentage If “Solid on” is selected in #38, LED (Default) ring will light up with background color setting in #40. If “Power wheel” is selected in #38, LED ring will light up in 4 levels. If “cycling”...
Page 25
Purple White (Default) Background color of RGB LED Other If “other” is selected, the background color is set by RGB via software. Pink Orange Yellow Green Blue Sky blue Data Color for RGB LED Purple White (Default) Other If “other” is selected, the data color is set by RGB via software.
Page 26
Blue Sky blue Purple White (Default) Background color of RGB LED only available when data Presentation of data color is set to Energy source (Grid-PV-Battery). Other If “other” is selected, the background color is set by RGB via software. For minute setting, the range is from 00 to 59.
Page 27
USB Function Setting Follow below steps to upgrade firmware. N in product overview Procedure LCD Screen Step 1: Insert an USB disk into the USB port ( ). Press and hold “ ” button for 3 seconds to enter USB Function Setting Mode. It will show ”...
Display Setting The LCD display information will be switched in turns by pressing “ ” or “ ” key. The selectable information is switched as the following table in order. Selectable information LCD display Input Voltage=230V, Input frequency=50Hz Utility voltage/ Utility frequency PV1 voltage=180V, PV1 current=8.0A, PV1 power=1440W PV voltage/ PV...
Page 29
Selectable information LCD display Battery voltage=54.0V, Floating charging voltage=54.0V, Charging current=7.8A Battery voltage, charging stage/ Configured battery Battery voltage=50.0V, Low DC cut-off voltage=42.0V, Discharging parameters/ Charging current=10A or discharging current Default Display Screen Output voltage=230V, Output frequency=50Hz Output voltage, load in VA, load in Watt switch Load in VA=2.0KVA, Output frequency=50Hz every 5 second/...
Page 30
Selectable information LCD display Load in Watt=1.9KW, Output frequency=50Hz Output voltage, load in VA, load in Watt switch every 5 second/ Output frequency Default Display Real date 2020-08-18. Screen Real date. Real time 11:31. Real time. PV energy generated today =8Wh. PV energy generated today...
Page 31
Selectable information LCD display PV energy generated this month = 8kWh. PV energy generated this month PV energy generated this year = 108kWh, PV energy generated this year Total PV energy generation = 108kWh. Total PV energy generation Main CPU version 00050.72. Main CPU version checking...
Selectable information LCD display Secondary CPU version 00022.01. Secondary CPU version checking Operating Mode Description Operating mode Behaviors LCD display Battery is charged by utility. Standby mode Note: Battery is charged by PV energy. *Standby mode: The inverter is not turned on yet but at this time, the inverter can charge battery without AC No output power, solar...
Page 33
Battery is charged by PV energy and feed PV energy to grid. Standby mode Note: *Standby mode: The inverter is not turned on yet but at this time, the inverter can charge battery without AC No output power, solar or utility charger output.
Page 34
PV energy and utility charge battery, and utility provides power to load. PV energy charges battery, utility and PV energy provide power to the load. Output power from Line Mode utility. Charger available PV energy charges battery, PV energy provides power to the load and feeds remaining energy to the grid.
Page 35
PV energy charges battery and provides power to the load. Output power from Battery mode battery or PV Battery provides power to the load. PV provides power to the load. Only PV mode Output power from PV No charging. Fault mode Note: No output, no *Fault mode: Errors are...
Page 36
Warning Indicator Warning Code Warning Event Icon flashing Fan locked Over temperature Battery over charged Low battery Overload Inverter power derating Battery is not connected Communication lost between com. port and control board...
Page 37
Faults Reference Code Fault Code Fault Event Icon on Fan is locked. Over temperature Battery voltage is too high. Battery voltage is too low. Output is short circuited. Output voltage is abnormal. Overload time out. Bus voltage is too high. Bus soft start failure.
CLEARANCE AND MAINTENANCE FOR ANTI-DUST KIT Overview Every inverter is already installed with anti-dusk kit from factory. Inverter will automatically detect this kit and activate internal thermal sensor to adjust internal temperature. This kit also keeps dusk from your inverter and increases product reliability in harsh environment.
TROUBLE SHOOTING Problem LCD/LED/Buzzer Explanation / Possible cause What to do Unit shuts down LCD/LEDs and buzzer automatically will be active for 3 The battery voltage is too low 1. Re-charge battery. during startup seconds and then (<1.91V/Cell) 2. Replace battery. process.