3. After the MDU screen starts, set the language, time, date, network parameters, and system
parameters by using the Setting Wizard.
4. After the quick settings are complete, if the monitoring page displays abnormal alarms, clear
them.
5. Switch on the input circuit breakers on the front panel of the PDC.
6. Switch on the output circuit breakers in the PDC in sequence to power on the corresponding
devices and check whether the monitoring parameters on the display panel are correct.
7. (Optional) Power off the PDC.
(1) Switch off the output circuit breakers in the PDC.
(2) Switch off the upstream input circuit breakers.
The power-on commissioning personnel must be at least two qualified electricians, one
performing operations while the other monitors the operations and warns off irrelevant persons.
IT Power Distribution Input
Indicators
IT Power Distribution Input
Circuit Breakers
IT Power Distribution SPD and
SPD Circuit Breakers
IT Power Distribution Output
Circuit Breakers
Power Distribution Monitoring
Boards
Air Conditioner Power
Distribution Input Indicators
Air Conditioner Power
Distribution Input Circuit
Breakers
Lighting Output Circuit Breaker
Power Distribution Monitoring
Boards
配电监控板
Power Distribution Monitoring Boards
Air Conditioner Power Distribution
SPD and SPD Circuit Breakers
Air Conditioner Power Distribution
Output Circuit Breakers
Power Distribution Monitoring Boards
9