IRRADIANCE SENSOR APPLICATION

With reference to Picture 4, in order to use an irradiance and temperature sensor, please
connect the irradiance output to the "Analog Input 1" terminal; temperature to the "Analog
Input 2" terminal; GND on any of the available GND connections.
2
The supported input ranges for the sensor are (0 ~ 1200) W/m
and (-20 ~ +80)°C
Please tie to PE
the shield of the sensor's cable either on this device side, or on
transducer side not on both sides.
Once the setup described in the previous chapters is accomplished, the Irradiance sensor
values are available through the software SunVision (please refer to its user's manual).