RSD PEFS-24V-CN Series 1 Scope and General The manual only used to PEFS-24V-CN Series Panel-level Rapid Shutdown(DC 24V) Control Box. Version Date Remark Chapter V1.0 2021-10-15 First Edition 4 Installation & Connection/ V2.0 2022-04-20 Content Modified 5 Technical Specification 3 Introduction V3.0...
RSD PEFS-24V-CN Series PEFS-24V-C180 ② Control Box External Power Supply PEFS-24V-C480 ① DC IN 4 Installation & Connection 1) Open the box, take out PEFS-24V-CN and parts, read this manual. Product Cable L-shaped Clasps Manual * 2-core wire 20/30/100m Optional * PEFS-24V-C60/C180 Type provide 2) Prepare materials and tools.
Page 5
RSD PEFS-24V-CN Series 3) The installation modes of PEFS-24V-CN are divided into the following two situations. Control Box Include Power Supply (Take PEFS-24V-C60 as an example) a) Align the round hole of the L-shaped calsp with the round hole of the box and fix them with screws.
Page 6
RSD PEFS-24V-CN Series b) Mount the control box to the appropriate location through the gourd-shaped hole. installation location(e.g. wall) c) Wiring PEFS-24V-C480 does not have a power supply, so an external power supply is required to power the control box.
RSD PEFS-24V-CN Series 5 Technical Specification Control Box (Include Power Supply) Model PEFS-24V-C60 PEFS-24V-C180 Operating AC Voltage Range 100 V-240 V Norminal Frequency 50/60 Hz Output Voltage 24V DC Max. Output Current 2.2A 8.8A 24Vdc Control Cable Size 0.823 mm2 / 18 AWG...
RSD PEFS-24V-CN Series 6 Trouble Shooting Problem Possible Cause Possible Solution No mains supply Check area utility operational Check mains ON (LED OFF) Check mains fuse Check mains voltage between L&N marked terminals PEFS-24V-CN power supply failure Check 24VDC between + & - marked terminals...