Daikin Altherma EWSAH06DA9W Installation Manual page 15

Hide thumbs Also See for Altherma EWSAH06DA9W:
Table of Contents

Advertisement

#
Layout
6 Dual cable power supply (= split power
supply)
+
Preferential kWh rate power supply with
separate normal kWh rate power supply
C5
C3
C2
C1
X2M
X5M
C1: Normal kWh rate power supply for the
backup heater (1N~ or 3N~)
C2: Preferential kWh rate power supply
contact
C3: Separate normal kWh rate power
supply for the hydro (1N~)
C4: Connection of X11Y
C5: Preferential kWh rate power supply
for the compressor (1N~)
(a)
See
"3.2.1 To open the indoor
(b)
Types of preferential kWh rate power supply:
INFORMATION
Some types of preferential kWh rate power supply require
a separate normal kWh rate power supply to the indoor
unit. This is required in the following cases:
▪ if the preferential kWh rate power supply is interrupted
when active, OR
▪ if no power consumption of the indoor unit is allowed at
the preferential kWh rate power supply when active.
Detail C1: Factory-mounted power supply cable
Wires: 3N+GND, OR 1N+GND
Maximum running current: Refer to name plate on unit.
Connect the factory-mounted power supply cable to a 1N~ or 3N~
power supply.
EWSAH/X06DA9W
Daikin Altherma 3 WS
4P675759-1 – 2021.10
(a)
Open the unit
(b)
a
e
b
f
d
c
Z1F
unit" [ 4  6].
a
b
1N~
1
3
5
7
I
I
I
I
F1B
2
4
6
8
Q1DI
L
N
1N~, 50 Hz, 230 V AC
a
Factory-mounted power supply cable
b
Field wiring
F1B
Overcurrent fuse (field supply). Recommended fuse for
1N~: 4‑pole, 32 A fuse, C curve. Recommended fuse for
3N~: 4‑pole, 16 A fuse, C curve.
Q1DI
Earth leakage circuit breaker (field supply)
Detail C2: Preferential kWh rate power supply contact
Wires: 2×(0.75~1.25 mm²)
Maximum length: 50 m.
Preferential kWh rate power supply contact: 16 V DC
detection (voltage supplied by PCB). The voltage-free contact
shall ensure the minimum applicable load of 15 V DC, 10 mA.
Connect the preferential kWh rate power supply contact (S1S) as
follows.
5 Electrical installation
3N~
OR
1
3
5
7
I
I
I
I
F1B
2
4
6
8
Q1DI
L1
L2 L3
N
3N~, 50 Hz, 400 V AC
S1S
X5M
Installation manual
15