Siemens RUGGEDCOM RX1511 Installation Manual page 49

Simatic net rugged multi service platforms
Hide thumbs Also See for RUGGEDCOM RX1511:
Table of Contents

Advertisement

Certification
6.2 EMC and Environmental Type Tests
a
Siemens-specified severity levels.
EMC Immunity Type Tests for IEEE 1613
Note
RUGGEDCOM products meet Class 1 requirements for copper Ethernet
configurations and Class 2 for fiber Ethernet configurations. Class 1 allows for
temporary communication loss, while Class 2 requires error-free and interrupted
communications.
Environmental Type Tests
40
Test
HV Impulse
Description
HV Impulse
Dielectric Strength
Fast Transient
Oscillatory
Radiated RFI
ESD
Test
IEC 60068-2-1
Cold Temperature
IEC 60068-2-2
IEC 60068-2-30
IEC 60255-21-1
IEC 60255-21-2
Description
Signal ports
DC Power Ports
AC Power Ports
Signal ports
DC Power Ports
AC Power Ports
Signal ports
DC Power Ports
AC Power Ports
Signal ports
DC Power Ports
AC Power Ports
Earth ground ports
Signal ports
DC Power Ports
AC Power Ports
Enclosure ports
Enclosure Contact
Enclosure Air
Description
Test Ad
Dry Heat
Test Bd
Humidity (Damp
Test Db
Heat, Cyclic)
Vibration
Shock
Bump
Test Levels
5 kV (Failsafe Relay output)
5 kV
Test Levels
5 kV (Failsafe Relay Output)
5 kV
2 kV
1.5 kV
2 kV
± 4 kV @ 2.5 kHz
± 4 kV
2.5 kV common mode @1MHz
2.5 kV common
1 kV differential mode @ 1 MHz
35 V/m
± 8 kV
± 15 kV
Test Levels
-40 °C (-40 °F), 16 Hours
85 °C (185 °F), 16 Hours
95% (non-condensing),
55 °C (131 °F), 6 cycles
2 g @ 10-150 Hz
30 g @ 11 ms
10 g @ 16 ms
RUGGEDCOM RX1511
Installation Manual, 04/2022, C79000-G8976-1056-22
Severity
Levels
Severity
Levels
 
 
 
Class 2
Class 2
Class 1

Advertisement

Table of Contents
loading

Table of Contents