About these operating instructions These operating instructions are part of the product. Mayser Polymer Electric accepts no responsibility or warranty claims for damage and consequential damage due to failure to observe the operating instructions. Ä Read the operating instructions carefully before use.
Symbol Meaning Danger symbols and information DANGER Immediate danger leading to death or serious injury. CAUTION Possible danger which may lead to minor injury or damage to property. Information on easier and safer working practices. Intended use The control unit is designed for processing the signals of a pressure-sensitive protec- tion device (PSPD).
Ä Do not overload control unit Ensure that the specified switching current is not exceeded. Ä In the event of a fault, put out of operation In the event of malfunctions and visible damage, put the control unit out of oper- ation by decommissioning it.
Product overview Connections Blue Green Yellow Orange Brown Connections: Terminals: Supply voltage 1, 5 Output 6, 5 Sensor 1 2, 3 Sensor 2 4, 3 Function, installation and commissioning Function The control unit has two monitoring circuits, which operate one output circuit. The electronics monitor the electrical resistance of the sensors, which have a defined closed-circuit current.
Installation Danger of injury from electric shock! DANGER Ä Disconnect all devices and live parts in the immediate environment from the power supply and secure them to prevent them from being switched on again (see relevant operating instructions). Ä Check whether all devices and parts are de-energised. Impaired operation due to overheating CAUTION If the control unit overheats, operation of the protection device may be impaired.
2. Wire the sensors, relay contacts and supply voltage to the cable terminals. Output Sensor 1 Sensor 2 Overall safety endangered CAUTION Overall safety is affected by the quality and reliability of the interface between the protection device and the machine. Ä...
Page 9
2. Activate sensor 1. Output is set to HIGH 3. Repeat step 1. 4. Activate sensor 2. Output is set to HIGH 5. Repeat step 1. 6. Disconnect sensor 1. Output is set to HIGH 7. Repeat step 1. 8. Disconnect sensor 2. Output is set to HIGH 9.
Recommissioning DANGER Danger of injury! Ä Never start your machine as long as the danger remains. Automatic reset Control unit RSV 206/1 The control unit works without a reset. If the sensor is released after activation, the output returns to “LOW” after a delay t Control unit RSV 206/2 The control unit works without a reset.
Ä Replace sensor If supply voltage is correctly connected and Ä Replace control unit sensor is OK: control unit is faulty Still unable to remedy the fault? Ä Contact Mayser-Support: Tel. +49 731 2061-0. 170912 v3.1cd Operating instructions SG-RSV 206/X Page11/14...
Page 12
= 1k2 ±5% 2. Measured resistance deviates signifi- cantly Ä Replace sensor Control unit faulty Ä Replace control unit Still unable to remedy the fault? Ä Contact Mayser-Support: Tel. +49 731 2061-0. Page 12/14 Operating instructions SG-RSV 206/X 170912 v3.1cd...
Replacement parts Overall safety endangered CAUTION If the sensor and control unit are not replaced using original parts from Mayser, op- eration of the protection device may be impaired. Ä Only use original parts from Mayser. Disposal The control units produced by Mayser are professional electronic tools exclusively in- tended for commercial use (known as B2B devices).
Technical data SG-RSV 206/1 SG-RSV 206/2 Testing basis ISO 13849-1, 72/245/EEC Connecting voltage U 8 to 32 V DC 8 to 32 V DC Voltage tolerance – – Nominal current 5 to 16 mA 6 to 24 mA Nominal frequency – – External fuse protection 100 mA time-lag 100 mA time-lag Power consumption <...