ABB Lon SPA-ZC 100 Installation Manual page 10

Table of Contents

Advertisement

SPA-ZC 100
10
Ç
Lon
/SPA Gateway
Installation Manual
7KH SLQ QXPEHUV RI WKH 63$EXV56 FRQQHFWLRQ DUH
Pin
1
DATA A, data signal pair, signal A (+)
2
DATA B, data signal pair, signal B (-)
3
RTS A, request to send signal pair, signal A (+)
4
RTS B, request to send signal pair, signal B (-)
7
GND, signal ground for the power supply
8
+5V, optional power supply for the SPA-ZC 100
9
+8V, power supply for the SPA-ZC 100
7KH SLQ QXPEHUV RI WKH 63$EXV77/ FRQQHFWLRQ DUH DV IROORZV
Pin
2
RXD, data from the SPA-bus device
3
TXD, data to the SPA-bus device
7
GND, signal ground for the power supply
8
+5V, optional power supply for the SPA-ZC 100
9
+8V, power supply for the SPA-ZC 100
SPA-ZC 100
1
2
3
4
8
7
9
9-pin female D-connector
)LJ 
,QWHUIDFH FDEOH 63$=&  WR 63$EXV GHYLFH ZLWK 56 RU
77//RJLF LQWHUIDFH
7KH SLQ QXPEHUV RI WKH 63$EXV56 FRQQHFWLRQ DUH DV IROORZV
Pin
2
TXD, data to the SPA-bus device
3
RXD, data from the SPA-bus device
5
GND, signal ground for the power supply
4
+12V, power supply for the SPA-ZC 100
8
+5V, optional power supply for the SPA-ZC 100
9
-12V, not used by the SPA-ZC 100
Usage
Usage
SPA device, RS-485 or TTL
+5V
GND
+8V
9-pin male D-connector
Usage
1MRS 750741-MUM
1
2
3
4
8
7
9
int_cablers485

Advertisement

Table of Contents
loading

Table of Contents