Auto-tune pid temperature controller

Advertisement

GEMO
Press for 2 sec.
CodE
SET
Back
Press "Back"
H.hys
to return to the
SET
top of
parameters
programming
A.hys
block
SET
Pb.C
SET
Ct
SET
H.Hys
not 0
ti
SET
td
SET
UP.L
SET
Lo.L
SET
oFFS
SET
AL.tY
SET
AL.tY=
Abs,-Abs,
r.ALr/
SnS.O,
SET
b.ALr
SnS.F
C-t
SET
L.dSP
SET
H.Hys
o.Sht
not 0
SET
SECU
SET
End Prog.
Error Messages:
Fail: Sensor failure or sensor selection wrong
E.FLS: Hardware failure
E.CAL: Hardware failure
E.EPr: Memory failure
Gürbüzoğlu Elektronik San. ve Tic. Ltd. Şti.
Çamlıtepe Cad. No:297 / 3-4 Siteler, Ankara, Türkiye
Tel: +90-312-3503900, Fax: +90-312-3511117
PROGRAMMING PARAMETERS
+
SET
Upper Display
Enter 162 to pass
Enter 162
to parameter prog. mode
Heat Hysteresis (
0 .. 50
o
C
PID is active if set to 0
1 .. 50
o
C
Alarm Hysteresis (
Proportional Band in (
5 .. 150
o
C
Control period (sec)
1 .. 200 sec
Integral Time: in min:sec
0:00 .. 30:00
If set to 0:00, P, PD is
min:sec
active (integral OFF).
Derivative Time: in min:sec.
0:00 .. 10:00
If set to 0:00, P, PI is
min:sec
active (derivative OFF).
Upper limit value for Lo.L,
H.SET and A.SET. Upper
Lo.L ..
Upper Scale (
o
C)
Scale value differs according
to the selected sensor type.
Lower limit value for UP.L,
Lower Scale ..
H.SET and A.SET. Lower Scale value
UP.L (
C)
o
differs according to the selected
sensor type.
Offset Value; Offset is directly added
-100 .. 100
O
C
to the measured value. This feature shall
be used for user calibration. Normally set to 0.
Alarm Type:
Abs,rel,bnd,bn.i
Abs: Absolute
-Abs,-rel,
rel: Relative
-bnd,-bn.i,
bnd: band
SnS.O, SnS.F
bn.i: band inhibit
Relative or band Alarm
-100 .. 100
O
C
Value. Displayed if AL.ty is
other then Abs or –Abs.
If C-t is not 0, ramping starts after power on. SET value
0.0 .. 300.0
is incremented or decremented C-t degrees per minute
o
C / min
until SET reaches H.SEt or C.SEt.
yes: Lower display ON
yes .. no
no: Lower display OFF
Over shoot reduction: All options other than "OFF" may help to reduce over
shoot more but also may increase instability around SET point. For this reason;
First try "OFF" option then 10.0->5.0->3.0->1.0->0.2 options if needed.
OFF, 10.0,
5.0, 3.0,
Options 1.0 and 0.2 are most sensitive and may result more instability around
1.0, 0.2
SET point among other options. With this parameter, over shoot is not allowed
more than; OFF: not limited, 10.0: 10 , 5.0: 5 , 3.0: 3 , 1.0: 1 , 0.2: 0.2 degrees
(over SET point).
AH: ALARM SET and HEAT SET may be SET,
AH, -H, A-, --
-H : Only HEAT SET may be SET,
-A : Only ALARM SET may be SET,
-- : ALARM SET and HEAT SET may not be SET.
CodE
o
C):
SET
"tunE"
flashes
o
C)
• Before starting Auto-tune, adjust H.SET.
• Process value may exceed H.Set during auto-tuning.
• After auto-tuning, control form automatically switches
C)
o
to PID mode.
• Auto-tuning is stopped (interrupted) any time by
pressing any key. In this case, the parameters before
auto-tuning is valid.
• Auto-tuning may not always determine the best values
for your process.
CodE
SET
"YES" / "nO"
• To return to factory settings:
Code > 555 > select "yes" >
Press "SET"
-Abs: Absoloute, invert out SnS.O: Sensor failure
-rel: Relative, invert out
-bnd: band, invert out
-bn.i: band, invert out
3
Upper Display
Enter "262"
to start
auto-tune
Upper Display
Factory SET Values:
H.SEt: 100
Enter "555"
A.SEt: 400
for factory
H.hys: 0
o
reset
A.hys: 3
o
Pb.C: 30
Ct: 4 sec
ti: 5:00 min:sec
td: 1:00 min:sec
UP.L: 400
Lo.L: 0
o
C
oFFS: 0
o
AL.tY : rel
r.ALr: 3
o
C
C-t: 0.0
o
C / min
L.dSP: yes
o.Sht: oFF
SECU: AH
Continuous out
SnS.F: Sensor failure
Flashing out
http://www.gemo.com.tr.