Indoor Floor Area Requirements
Table Ⅰ – Maximum refrigerant charge allowed in a room
Aroom (m2)
H=1.15m
1
0.265
2
0.530
3
0.794
4
1.059
5
1.324
6
1.589
7
1.738
8
1.858
9
1.971
10
2.078
11
2.179
12
2.276
• For intermediate H values, the value that corresponds to the lower H value from the table considered.
Example:
For H=1.25 m, the value that corresponds to H=1.20 m is considered.
• For intermediate Aroom values, the value that corresponds to the lower Aroom value from the table is considered.
Example:
For Aroom =10.5 m2, the value that corresponds to Aroom =10 m2 is considered.
Maximum refrigerant charge in a room / mmax (kg)
H=1.20m
H=1.30m
0.276
0.299
0.553
0.599
0.829
0.898
1.105
1.197
1.382
1.497
1.658
1.796
1.814
1.965
1.939
2.101
2.057
2.228
2.168
2.349
2.274
2.463
2.375
2.573
H=1.40m
H=1.50m
0.322
0.345
0.645
0.691
0.967
1.036
1.289
1.382
1.612
1.727
1.934
2.072
2.116
2.267
2.262
2.424
2.399
2.571
2.529
2.710
2.653
2.842
2.771
2.969
4
H=1.60m
H=1.70m
0.368
0.391
0.737
0.783
1.105
1.174
1.474
1.566
1.842
1.957
2.210
2.349
2.418
2.570
2.585
2.747
2.742
2.914
2.891
3.071
3.032
3.221
3.166
3.364
H=1.80m
0.414
0.829
1.243
1.658
2.072
2.487
2.721
2.909
3.085
3.252
3.411
3.562